LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 34

Advertising
background image

LAARS Heating Systems

Page 30

Section 7

ELECTRICAL CONNECTIONS

WARNING

The NeoTherm LC appliance must be electrically

grounded in accordance with the requirements of

the authority having jurisdiction or, in the absence

of such requirements, with the latest edition of the

National Electrical Code, ANSI/NFPA 70, in the

U.S. and with latest edition of CSA C22.1 Canadian

Electrical Code, Part 1, in Canada. Do not rely

on the gas or water piping to ground the metal

parts of the boiler. Plastic pipe or dielectric unions

may isolate the boiler electrically. Service and

maintenance personnel who work on or around the

boiler, may be standing on wet floors and could be

electrocuted by an ungrounded boiler. Electrocution

can result in severe injury or death.

Single pole switches, including those included in

safety controls and protective devices, must not be

wired in a grounded line.
All electrical connections are made on the terminal

blocks that are located inside the control panel.

Note - All internal electrical components have been

prewired. No attempt should be made to connect

electrical wires to any other locations except the

terminal blocks.

The wiring connections are shown in Figures 19 and 21

.

Note - Do not make and break the line voltage to the

NeoTherm LC as a signal to call for heat.

On a system operating as a Lead/Lag installation -

A “call for heat/ end call for heat”

must be connected

to the Primary TT or Interlock terminals (terminals 5

and 6 on TB7) on the controller which is acting as the

Lead/Lag master.
On a boiler operating individually -

A “call for heat/ end call for heat”

must be connected

to the Primary Thermostat terminals (terminals 5

and 6 on TB7). Any jumper to the System terminals

(terminals 3 and 4 on TB6) must be removed. For

details, see Section 9.

Some NeoTherm LC components are designed to

have constant voltage during normal operation. If

the NeoTherm LC’s supply voltage is toggled as

a call for heat signal, premature failure of these

components may result.
The NeoTherm LC does not recognize 4 mA as a signal

to shut off. If the call for heat is not connected between

the field interlock terminals, NeoTherm LC will remain in

low fire when it sees 4 mA as a modulating signal.

Caution

The supply voltage to the NeoTherm LC must not

be disengaged, except for service or isolation, or

unless otherwise instructed by procedures outlined

in this manual. To signal a call for heat, use the

correct terminals as instructed in Section 9.

7.1

Main Power

For the convenience of the installer, a junction box

has been placed at the rear of the boiler (internal)

for power connections. These connections include

three pre-stripped wires (black, white and green) for

power connections.
For Model 1000 use a single 120-volt 15 Amp fused

supply. For Model 1700 use a single 120-volt 30

Amp fused supply.

7.2

Pump Connections

The NeoTherm LC energizes the appropriate pump

contacts when it receives a call for heat or domestic

hot water. Once the call for heat or DHW is satisfied,

the pump will remain on for the defined pump

overrun time.

Note - The contacts for the System and DHW

pumps are dry contacts. Appropriate voltage must

be supplied to the System and DHW pumps for

proper operation.
The Boiler pump is controlled in two different ways,

depending on the NeoTherm LC model:
• On NeoTherm LC 1000 units the appliance will

supply 120V single-phase power to the Boiler

pump. The current supplied by this source cannot

exceed 7.4 FLA. If more current is required, an

additional relay/pump contactor must be installed.

Wire the relay so it is energized from the contacts

on the boiler to allow the pump to be turned on

and off with the demand.

• On NeoTherm LC 1700 units the appliance

will include a dry contact to operate the Boiler

pump. The current from an alternate power

source through this contact cannot exceed 7.4

FLA at 120V. If more current is required, then an

additional relay/pump contactor must be installed

and controlled by the boiler pump dry contacts.

Advertising