LAARS Heating Systems

Page 86

Label

Description

How to Reach

Lead lag on

hysteresis

When the Lead/Lag function is enabled, the

control system will not fire the boilers until the

temperature at the System sensor drops to the

Lead/Lag CH setpoint minus a hysteresis value

(normally about 10°F).

If Lead/Lag enabled –

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen>

Lead lag P

gain

This is part of the damping function

(“Proportional”) used when the controller

interprets the input from the System sensor.

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen> Advanced Settings button/ Left-

or Right- arrow buttons <Modulation

screen>

Lead/Lag

Slave Enable

Select Enable Slave for Built-in Lead/Lag

Master. Be sure this is turned on for each

controller in the system.

<’home’ screen> Select a controller

<Status Summary screen> Configure

button <Configuration Menu> Select line

for LL Slave Configuration <Lead/Lag

Slave Configuration screen>

Lead/

Lag Slave

Sequence

Order

Enter the position of this Slave in the sequence.

Be sure to enter this for each Slave in the

system.

<’home’ screen> Select a controller

<Status Summary screen> Configure

button <Configuration Menu> Select line

for LL Slave Configuration <Lead/Lag

Slave Configuration screen>

Lead/

Lag Slave

Modbus

Address

Each slave must have a unique Modbus address.

Be sure to enter this for each controller in the

system.

<’home’ screen> Select a controller

<Status Summary screen> Configure

button <Configuration Menu> Select line

for LL Slave Configuration <Lead/Lag

Slave Configuration screen>

Lead/Lag

Outdoor

Reset Enable

Enable = Outdoor Reset feature turned on

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen> Advanced Settings button/ Left-

or Right- arrow buttons <Outdoor Reset

screen>

Lead/Lag

Outdoor

Reset

low water

temperature

This parameter is used as the normal setpoint

above the point where Outdoor Reset stops

adjusting for a higher outdoor temperature (the

Max. Outdoor Temperature value)

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen> Advanced Settings button/ Left-

or Right- arrow buttons <Outdoor Reset

screen>

Lead/Lag

Outdoor

Reset max

outdoor

temperature

If Lead/Lag is enabled, this is the maximum

outdoor temperature at which the Outdoor Reset

feature will be active.

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen> Advanced Settings button/ Left-

or Right- arrow buttons <Outdoor Reset

screen>

Lead/Lag

Outdoor

Reset min

outdoor

temperature

If Lead/Lag is enabled, this is the minimum

outdoor temperature at which the Outdoor Reset

feature will be active.

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen> Advanced Settings button/ Left-

or Right- arrow buttons <Outdoor Reset

screen>