LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 99

Advertising
background image

NeoTherm LC Boilers and Water Heaters

Page 95

12.1.2 Flap Valve Status Check
Each boiler includes two burners, and each burner

has a flap valve. See Fig. 123.
If one burner in a boiler is operating, and the other

is not, the flap valve for the burner that is off will

remain closed to prevent air from moving backwards

through the burner that is not operating. Before the

Lead/Lag Master controller will allow the system

to operate, it must be able to determine whether

each of these flap valves is open or closed. If the

controller cannot find a signal from one of the

flap valves, the control system will act to prevent

backflow by energizing the blower of the control

with the bad flap valve. If this cannot be done the

control will not allow the whole system to run. If

the flap valve identifications are not set correctly, the

control system will present a “HOLD 119 – Control

Interaction Fault” on the display. For this reason, it

is important that all of the flap valves be identified

correctly.

12.2 About Lockouts, Holds, and

Alerts

The control system on the NeoTherm LC responds

to three kinds of trouble indications:

A “lockout” is caused by a serious problem

that might involve a safety issue. Once

the controller enters a lockout, the burners

will shut down, and will not be allowed to

run again until the cause of the problem is

corrected, and you reset the control system.

The controller will also trigger a lockout if you

change a safety-related parameter, but do not

finish the “verification” process. (For more

information on verification, see Section 8.8)

Primary

burner

Primary

controller

Flap

valve

Flap

valve

Secondary

controller

Secondary

burner

Operator

interface

Boiler 1

Fig. 123 - Flap Valve Arrangement

During a lockout condition, the image of the

affected controller on the ‘home’ screen will

appear in red. A bell symbol will appear in the

upper left-hand corner of the control screen.

The system maintains a “history” of the 15

most recent lockouts.

The system may enter a “hold” for a period

of time before locking out. This allows the

controller to see if the error becomes resolved

prior to the hard lockout. Holds can occur

while the boiler is operating.

An “alert” indicates that some feature of the

control system’s operation was not correct,

delayed or waiting for a response. This

indicates a change in state of the control

system and doesn’t necessarily mean there

is a problem. For example, Alerts occur as

the fan speed transitions from the pre-purge

RPM to the startup RPM. This indicates that

the control system is waiting for a condition

to be satisfied. No Reset is required to

recover from an alert. The system maintains

a “history” of the 15 most recent alerts.

Sometimes it can be helpful to check this list

as a troubleshooting aid.

12.2.1 Responding to a Lockout, Hold, or

Alert

1. If a problem occurs while the system is

starting up, the system will declare a Hold.

A brief explanation of the cause of the Hold

will appear in an orange bar across the bottom

of the screen. If you tap the orange bar, the

system will present more information about

the Hold.

Advertising