LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 121

Advertising
background image

NeoTherm LC Boilers and Water Heaters

Page 117

During the Initiate Period:

All of the checks made under Synchronization,

plus:

Locks out if A/C line power errors occur.

Locks out if four-minute Initiate period has

been exceeded.

During the Standby Period:

All of the checks made under Synchronization,

plus:

Locks out if the Flame signal is present after

240 seconds.

Locks out if the Preignition Interlock is open

for more than 30 seconds.

Locks out if the Interlock Start check feature

is enabled and the Interlock String (including

the Airflow Switch) is closed for 120 seconds

with the controller closed, perhaps indicating a

jumpered or welded Interlock.

Locks out if the Main Valve terminal is

energized.

Locks out if an internal system fault occurs.

During the Prepurge Period:

All of the checks made under Synchronization,

plus:

Locks out if the Preignition Interlock opens

anytime during the Prepurge period.

Locks out if the Flame signal is detected for

more than 10 seconds during Prepurge.

Locks out if the Light Off Rate Fan RPM or

Low Fire Switch is not reached within four

minutes and fifteen seconds after the blower

is commanded to drive to the light off rate fan

RPM at the end of Prepurge.

Locks out if the Main Valve terminal is

energized.

Locks out if an internal system fault occurs.

During the Pre-Ignition Time:

All of the checks made under Synchronization,

plus:

Locks out if the Main Valve terminal is

energized.

During the Main Flame Establishing Period

(MFEP):

All of the checks made under Synchronization,

plus:

Locks out if no flame is present at the end of

the appropriate number of ignition retries.

Locks out if an internal system fault occurs.

During the Run Period:

All of the checks made under Synchronization,

plus:

Locks out if an internal system fault occurs.

Locks out if a safety-related parameter has

been changed, but the change has not been

verified and the controller has not been reset

using the button on the front of the control.

During the Postpurge Period.

All of the checks made under Synchronization,

plus:

Locks out if the Preignition Interlock does not

close in five seconds.

Locks out if the Main Valve terminal is

energized.

Locks out if an internal system fault occurs.

Locks out if flame is sensed 240 seconds after

the Run period.

Advertising