LAARS Heating Systems

Page 14

5. Locate the vent terminal so that it cannot

be blocked by snow. The installer may

determine that a vent terminal must be

higher than the minimum shown in codes,

depending upon local conditions.

6. Locate the terminal so the vent exhaust does

not settle on building surfaces or other nearby

objects. Vent products may damage surfaces or

objects.

7. If the boiler or water heater uses ducted

combustion air from an intake terminal located

on the same wall, see Figures 10 and 11 for

proper spacing and orientation.

If the vent termination is located in an area exposed

to high winds, an optional PVC tee (the same

diameter as the vent pipe) may be used. The tee’d

vent termination offers greater protection from wind

related operating issues.

3.3.2 Side Wall Combustion Air Terminal
The LAARS side wall combustion air terminal

must be used when the heater takes air from a side

wall. (See Table 3.) Contact Laars for AL29-4C

termination fittings. Consider the following when

installing the terminal. (See Figures 10 and 11).
1. Do not locate the air inlet terminal near a

source of corrosive chemical fumes (e.g.,

cleaning fluid, chlorine compounds, etc.).

2. Locate the terminal so that it will not be subject

to damage by accident or vandalism. It must be

at least 7 feet ( 2.1 m) above a public walkway.

3. Locate the combustion air terminal so that it

cannot be blocked by snow. The National Fuel

Gas Code requires that it be at least 12 inches

(30 cm) above grade, but the installer may

determine it should be higher, depending upon

local conditions.

4. If the NeoTherm LC is side-wall vented to the

same wall, locate the vent terminal at least 1

foot (0.3 m) above the combustion air terminal.

5. Multiple vent kits should be installed such that

the horizontal distance between outlet group

and inlet group is 36” (90 cm). (See Figure

10.)

6. The vent outlet must be at least 12” above the

top of the air inlet, and must be at least 36” (90

cm) horizontally from the air inlet. (See Figure

10.)

Fig. 11 - Minimum Venting Distance

IMPORTANT: All terminals must be placed so that they remain at least

12” above the expected snow line. Local codes may have more specific

requirements, and must be consulted. Refer to the NFPA54 National Fuel

Gas Code and your local codes for all required clearances for venting.