NeoTherm LC Boilers and Water Heaters

Page 85

Label

Description

How to Reach

Lead lag D

gain

This is part of the damping function

(“Derivative”) used when the controller

interprets the input from the System sensor.

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen> Advanced Settings button/ Left-

or Right- arrow buttons <Modulation

screen>

Lead lag

DHW

demand

switch

This indicates source of the aquastat signal used

to control the Domestic Hot Water loop.

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen> Advanced Settings button/ Left-

or Right- arrow buttons <Domestic Hot

Water screen>

Lead lag

DHW has

priority over

CH

Choose Central Heating priority or Domestic

Hot Water priority.

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen> Advanced Settings button/ Left-

or Right- arrow buttons <Domestic Hot

Water screen>

Lead Lag

DHW

priority

override time

If Domestic Hot Water has priority, this sets

how long the DHW loop will continue to have

control after the DHW demand stops.

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen> Advanced Settings button/ Left-

or Right- arrow buttons <Domestic Hot

Water screen>

Lead lag

DHW

setpoint

This is the setpoint used for Domestic Hot Water

when the Lead/Lag system is enabled.

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen>

Lead lag

DHW TOD

setpoint

This is a different setpoint used for Domestic

Hot Water when the Lead/Lag system is enabled

and the input from the Time Of Day switch is

“true.”

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen>

Lead lag I

gain

This is part of the damping function (“Integral”)

used when the controller interprets the input

from the System sensor.

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen> Advanced Settings button/ Left-

or Right- arrow buttons <Modulation

screen>

Lead lag

master

enable/

disable

One of the controllers must be set up as the

Lead/Lag Master to supervise the Lead/lag

system. Usually this is the Primary controller on

Boiler 1. The master function must be disabled

on all of the other controllers. See the section

on “About Lead/Lag.”

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen>

Lead lag off

hysteresis

When the Lead/Lag function is enabled, the

control system will not shut off the boilers until

the temperature at the System sensor rises to the

Lead/Lag CH setpoint plus a hysteresis value

(normally about 10°F).

<’home’ screen> Lead/Lag Master button

<Lead/Lag Master screen> Configure

button <Lead/Lag Master Configuration

screen> Advanced Settings button/ Left-

or Right- arrow buttons <Modulation

screen>