LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 20

Advertising
background image

LAARS Heating Systems

Page 16

3. As much as possible, close all building doors

and windows. Also close all doors between

the space in which the appliances remaining

connected to the common venting system are

located and other spaces of the building. Turn

on any clothes dryers or other appliances not

connected to the common venting system.

Turn on any exhaust fans, such as range hoods

and bathroom exhausts, so they will operate

at maximum speed. Do not operate a summer

exhaust fan. Close any fireplace dampers.

4. Place in operation the appliance being inspected.

Follow the lighting instructions. Adjust the

thermostat so the appliance will operate

continuously.

5. Test for spillage at the draft hood relief opening

after five minutes of main burner operation. Use

the flame of a match or candle, or smoke from a

cigarette, cigar or pipe.

6. After it has been determined that each appliance

remaining connected to the common venting

system properly vents when tested as outlined

above, return the doors, windows, exhaust fans,

fireplace dampers and any other gas burning

appliances to their previous conditions of use.

7. Any improper operation of the common venting

system should be corrected so that the installa-

tion conforms to the National Fuel Gas Code,

ANSI Z223.1/NFPA 54 and/or CSA B149.1,

Installation Codes. When resizing any portion

of the common venting system, the common

venting system should be resized to approach the

minimum size as determined using the appropri-

ate tables and guidelines in the National Fuel

Gas Code, ANSI Z223.1 NFPA 54 and/or CSA

B149.1, Installation Codes.

3.5

Outdoor Installation

The NeoTherm LC may only be installed outdoors

in applications where the outdoor temperature

doesn’t drop below freezing. For proper operation

in outdoor installations, the boiler must be equipped

with the inlet air and exhaust terminal kits listed in

Table 3C. The bottom panel cover plate must be

removed. Additional instructions are supplied with

the terminal kits.

3.6

Condensate Drain Trap

A condensate drain trap is included with the

NeoTherm LC and is designed to drain the boiler of

condensate. The vent condensate should be drained

through a drain tee located in the vent line. This will

help prevent excessive condensate from entering

the boiler condensate trap and preventing the boiler

from operating.
Connect a 3/4” PVC pipe between the drain

connection and a floor drain (or condensate pump if

a floor drain is not accessible).
The condensate drain must be installed to prevent

the accumulation of condensate. When a condensate

pump is not used, the tubing must continuously

slope downward toward the drain with no spiraling.
Consult local codes for the disposal method.

Caution

Condensate is mildly acidic (pH=5), and may

harm some floor drains and/or pipes, particularly

those that are metal. Ensure that the drain,

drainpipe, and anything that will come in

contact with the condensate can withstand the

acidity, or neutralize the condensate before

disposal.

Damage caused by failure to

install a neutralizer kit or to adequately treat

condensate will not be the manufacturer’s

responsibility.

Advertising