NeoTherm LC Boilers and Water Heaters

Page 113

12.4 Diagnostic Tests and Input/

Output Indicators

Two kinds of screens are grouped together in this

section:

• Detailed indications of the input and output

signals

• Diagnostic tests of the pumps and burner

modulation

Note that these functions apply to just one selected

controller.

How to get there –
Home Page <Select icon> Status Summary Screen

<Diagnostics button>

1. The buttons at the bottom of the screen select

the types of inputs and outputs displayed. The

Burner Control I/O button leads to Fig. 129.

Fig. 129 - Burner Control I/O Screen

A green dot indicates a function that is “on.”

2. Press the Digital I/O button to look at

functions where the functions are either “on”

of “off.” See Fig. 130.

Fig. 130 – Digital I/O Screen

3. The button for Analog I/O displays items that

change continuously between two limits. See

Fig. 131.

Fig. 131 - Analog I/O Screen

4. Press the button for Diagnostic Tests. The

Modulation test allows you to change the

rate at which the burner fires, and watch the

results. See Fig. 132.

Fig. 132 – Modulation Test

5. Press the Pump Test button. The Pump test

shows detailed information on the activity

of the three pumps that may be used by the

system.

Fig. 133 – Pump Test