NeoTherm LC Boilers and Water Heaters

Page 57

Job D - Disable the Lead/Lag Master

Function on the Lead/Lag Slaves

(This is an individual function – do this for each of the controls,
except the one used as the Lead/Lag Master. Use the separate
Touch Screen on each boiler.)

At the beginning of this section, we described

the Master and Slave arrangement used with the

Lead/Lag system. In the previous section, we

explained how to set up one controller as the Lead/

Lag Master. As we said, the controller used as the

Master (usually the Primary controller for Boiler 1)

also serves as a Slave (usually Slave 1). A single

controller performs both functions.
When the controllers arrive from the Laars factory,

they will all be configured as slaves. Your job in this

step is to disable the Lead/Lag Master function on

each of the controls, except for the one control that

will be used as the Lead/Lag Master – usually the

Primary control on Boiler 1.

1. From the ‘home’ screen (Fig. 59), press the

icon for the controller you want to work

with. In this example, we will start with the

Secondary controller for Boiler 1, and make

sure this is not set up as a Master.

Fig. 59 – ‘home’ screen

2. The system will take you to the Status

Summary screen.

Fig. 60 – Status Summary Screen

3. To disable the Master function on this

controller, press the Configure button. Figure

61 shows the Configuration screen.

Fig. 61 – Configuration Screen

4. Scroll down through the list until you find the

line for LL Master Configuration. See Fig. 62.

Fig. 62 – Lead/Lag Master Configuration


Press on the line for Master Enable. The

system will go to a separate screen and ask

you to login using a password. Enter the

password (see Section 8.2), return to the

Master Configuration screen, then press the

line for Master Enable again. Change the

entry to Disabled.

Don’t change any of the other entries on this

screen.

5. At this point, you have disabled the Master

function on one of the controllers. You will

need to repeat the process for each of the other

controllers in the system (except the Primary

Controller on Boiler 1).

Go to the Touch Screen on the next boiler.

Repeat steps 1 through 4 for the first controller

on that boiler.

6. Repeat the steps listed above for each of the

other controllers on the system. Disable the

Master function on each of them.