NeoTherm LC Boilers and Water Heaters

Page 59

Primary Control on Boiler 1 is “1.” If this

is not already set to “1”, enter the correct

number, then press OK.

WARNING

If the addresses are not assigned properly, the

system could fail to operate correctly, or it might

operate in an unsafe manner. This could lead to

property damage, personal injury or death.

10. Now you can use the same process to set the

address for the Secondary control for Boiler 1.

On the Control Setup screen (Fig. 65), press

the second line – NeoTherm LC Secondary.

Change the address to the correct address

taken from Table 3. In this case, the correct

address would be “2.”

11. Go to the Touch Screen for Boiler 2. Repeat

the process to change the addresses for

Boiler 2 Primary (address = 3) and Boiler 2

Secondary (address = 4).

12. Repeat steps 3 - 10 for each of the other

controllers connected to the system.

Job F - Set the Flap Valve IDs

(These are individual functions. Make the flap valve assignment
on each of the controllers. Use the Touch Screen on each of the
boilers.)

Do this on any system with multiple boilers.
Each boiler includes two burners, and each burner

has a flap valve. See Fig. 67.

A flap valve acts like a one-way valve or check

valve. If one burner in a boiler is operating, and

the other is not, one of the flap valves will close to

prevent exhaust air from moving backwards through

the burner that is not operating.
Before the Lead/Lag Master controller will allow

the system to operate, it must be able to determine

whether each of these flap valves is open or closed.

If the controller cannot find a signal from one of the

flap valves, the control system will act to prevent

backflow by energizing the blower of the control

with the bad flap valve. (The positive pressure from

the blower will prevent the exhaust air from moving

back through the burner.) If this cannot be done, the

Lead/Lag Master controller will not allow the whole

system to run. For this reason, it is important that all

of the flap valves be identified correctly.
Each controller in the system needs to know how

many controllers are included in the whole system.

You will need to enter this information in each of the

controllers separately.

Boiler 1

Boiler 2

Boiler 3

Boiler 4

Primary control

1

3

5

7

Secondary control

2

4

6

8

Table 13 – Modbus Control Addressing

Primary

burner

Primary

controller

Flap

valve

Flap

valve

Secondary

controller

Secondary

burner

Operator

interface

Boiler 1

Fig. 67 - Flap Valve Arrangement