LAARS Heating Systems

Page 32

The System pump connections are located on

terminal block 5 (5-6 on TB5) in the control panel.

(See Figure 20.) The System pump contacts are rated

for 120 VAC, 7.4 Amps. To use the contacts, power

must be supplied on one terminal with the other

terminal wired to the relay controlling the pump.
The DHW pump connections are located on terminal

block 5 (7-8 on TB5) in the control panel and are

rated for 120 VAC, 7.4 Amps. To use the contacts,

power must be supplied on one terminal, and the

other terminal wired to the relay controlling the

pump.
Additional 120 VAC circuits may be required for the

pumps.

7.3

24 VAC Transformer with Integral

Circuit Breaker

24 VAC is supplied by a transformer mounted on the

control panel. All 24 VAC power is supplied through

a circuit breaker that is part of the transformer. The

transformer is then connected to terminal blocks 1

and 2 (TB1 and TB2).

7.4

Signal Connections

See Section 9 for details on the following

connections:
• System sensor
• Call for heat/thermostat
• Outdoor air temperature sensor
• Aquastat for domestic hot water
• External control connections

7.5

Optional Field Connections

Optional components, such as low water cutoffs,

flow switches, additional high limits and other field

supplied devices can be installed as shown on the

wiring diagram (Fig. 22).

7.6 Ladder and Wiring Diagrams

See Figures 21 and 22.

Caution

When servicing controls, label all wires prior to

disconnection. Wiring errors can cause improper

and dangerous operation. Verify proper operation

after servicing

Table 10 - Electrical Data

Model

1,000

1,700

Voltage

120 V AC

120 V AC

Current - FLA

12 A

30 A

Current - Nominal

5 A

16 A