Page 73

Required tools: Screwdrivers, Torx bits, combustion

analyzer

In the rest of this section we will explain the setup

procedure in more detail.

1. On the gas valve for the Primary burner on the

boiler, locate the adjustments for the high fire

CO

2

and low fire CO

2

. See Fig. 98 and 99.

Table 17 lists the CO

2

readings you should see

at high fire and low fire.

2. To start the setup, turn on the call for heat.
3. Before you can set up the Primary burner, you

must shut off the Secondary burner. Go to the

‘home’ screen on the display. Press the icon

for the control labeled Secondary.

Fig. 100 – ‘home’ screen

4. The system will present the Status Summary

screen.

Fig. 101 – Status Summary Screen

5. Press the Operation button. The system will

present the Operation screen for the Secondary

burner.

Fig. 102 – Operation Screen

Press the Burner Enable switch in the upper

left-hand corner of the screen. Since you

selected the Secondary control for this boiler,

this will turn off the Secondary burner. The

system will ask you to log in as you do this.

6. Now you can work with the Primary burner

for this boiler. Press the Home icon to go back

to the ‘home’ screen on the display (Fig. 100).

Press the icon for the control labeled Primary.

7. The system will present the Status Summary

screen for the Primary burner. Press the

Operation button.

8. The system will present the Operation screen

for the Primary burner.

Fig. 103 – Operation Screen

Model

Gas Type

High Fire CO

2

Low Fire CO

2

Pressure Differential

1,000

Natural

8.5% ± 0.2

0.5% lower than high fire CO

2

0.5” to 1.2” wc*

Propane

9.5% ± 0.2

0.5% lower than high fire CO

2

0.5” to 1.2” wc*

1,700

Natural

9.0% ± 0.2

0.5% lower than high fire CO

2

0.5” to 1.2” wc*

Propane

10.0% ± 0.2

0.5% lower than high fire CO

2

0.5” to 1.2” wc*

* - Only check the pressures if there are problems getting the CO

2

and CO values in range.

Table 17 – CO

2

Range and Pressure Differential