NeoTherm LC Boilers and Water Heaters

Page 19

Section 5

PUMP REQUIREMENTS

5.1

NeoTherm LC Boiler Flow and Head Requirements

5.2

NeoTherm LC Water Heater Flow and Head Requirements

Table 7 - Water Flow Requirements

Table 8 - NeoTherm LC Water Heater Flow Data

Temperature Rise in °F

Model

20°F

25°F

30°F

35°F

40°F

45°F

Flow

GPM

H/L-Ft

Flow

GPM

H/L-Ft

Flow

GPM

H/L-Ft

Flow

GPM

H/L-

Ft

Flow

GPM

H/L-

Ft

Flow

GPM

H/L-Ft

1,000

95

30

75

20

62

15

54

11

48

9

42

7

1,700

161

41

129

27

107

19

92

14

81

11

72

9

Temperature Rise in °C

Model

11.0°C

13.7°C

16.5°C

19.3°C

22.0°C

24.7°C

Flow

LPM

H/L-m

Flow

LPM

H/L-m

Flow

LPM

H/L-m

Flow

LPM

H/L-m

Flow

LPM

H/L-m

Flow

LPM

H/L-m

1,000

359

9.0

283

6.0

234

4.5

204

3.3

182

2.7

159

2.1

1,700

609

12.3

488

8.1

405

5.7

348

4.3

306

3.3

272

2.7

Temperature Rise

Model

20°F

11.0°C

Flow GPM

H/L-Ft

Flow LPM

H/L-m

1,000

95

30

359

9.0

1,700

161

41

609

12.3

Notes -

Figures listed are for soft/normal water.

Maximum hardness of 10 grains per gallon allowed.