LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 6

Advertising
background image

LAARS Heating Systems

Page 2

Each controller and burner work together. Each

boiler includes two of these controller/burner

combinations.

Notice the different terms we are using here.

The term boiler refers to the whole appliance

– the complete NeoTherm LC 1000 or 1700.

Each boiler includes two separate controller/

burner pairs.

NeoTherm LC 1000 and 1700 units are always

set up for “Lead/Lag” operation. The term

“Lead/Lag” means that, as the heating load

increases, the control system brings additional

burners on automatically.

Touch

Screen

Boiler 1

Slave 4

Boiler 2

Slave 3

Slave 2

Lead Lag

Master and

Slave 1

Slave 6

Boiler 3

Slave 5

Slave 8

Boiler 4

Slave 7

Addr

1

Addr

2

Addr

3

Addr

4

Addr

5

Addr

6

Addr

7

Addr

8

Fig. 2 – Lead/Lag Arrangement in a Multiple-

Boiler Installation

On a multiple-boiler installation, each of the

individual boilers is still set up as shown in Fig. 1

above, but the controller/burner pairs on all of the

boilers are arranged in a “daisy chain.”

Up to four boilers, with up to eight controller/burner

pairs, can be connected in this way. See Fig. 2.

In all NeoTherm LC multiple-boiler installations,

just one of the Touch Screens is active. It can

communicate with all of the controller/burner pairs

in the system, so it displays information from all of

the burners. A single system sensor provides the

control input for the system.

All NeoTherm LC’s that are set up as a single

boiler will still uses a Lead/Lag operation. If the

heating load becomes too great for the first burner,

the control system automatically starts the second

burner.
To work with this control system, you will need

to understand the difference between two kinds of

control functions:

SYSTEM FUNCTIONS, Some of the

functions control all of the controller/burner

pairs, working together as part of the Lead/

Lag system. As an example, the setpoint for a

whole multiple-boiler system is set by a single

value: “Central Heat Lead/Lag Setpoint.”

By changing this one value, you change the

setpoint used by the whole system. The action

of all of the controller/burner pairs will refer

back to that single value.

On the Touch Screen, from the ‘home’ screen

you can reach all of the Lead/Lag functions by

pressing the View Lead Lag button. See Fig. 3.

INDIVIDUAL FUNCTIONS, Other functions

apply only to each separate controller/burner

pair. As an example, each controller/burner has

a name, and this can be changed.

The ‘home’ screen on the Touch Screen will

show icons for each of the controller/burner

pairs connected to the system. To reach one

of the functions for an individual controller/

burner, press the icon for that controller/

burner. On the following screen, press the

Configure button. This will take you to all of

the configuration options for that individual

controller/burner.

Press here to

see current

Lead/ Lag

performance

Press here

for individual

controller/

burner pairs

Press here

for Lead/ Lag

setup

Press here for

system setup

Fig. 3 – Going to Lead/Lag and Individual

Functions

Note – For individual functions, if you want to make

a change on all of the controller/burner pairs in the

system, you will have to go to each controller/burner

separately and repeat the change for each of them.

If there are eight controller/burners in the system,

and you want to make the same change on all of

them, go to each of the eight controller/burner pairs

separately.

As we go through the explanations in this manual,

we will point out whether a control function affects

the whole Lead/Lag system, or just an individual

controller/burner pair.
This has been just a quick introduction, but this

Advertising