Page 60

WARNING

If the flap valve identifications are not configured

correctly, this could cause the equipment to

malfunction. This could lead to personal injury or

death, and could damage the equipment. If the

configuration is not correct, the control system

will present an error – “HOLD 119 – Control

Interaction Fault” on the display, and will prevent

the boiler(s) from operating.

1. Let’s start by setting the Flap Valve ID for the

Primary control for Boiler 1. To do this, start

at the ‘home’ screen (Fig. 68). (To reach

the ‘home’ screen, press the Home icon in the

upper left corner of any screen.)

Fig. 68 – ‘home’ screen

2. Press the icon for the controller you want to

work with. The system will take you to the

Status Summary screen for that controller.

Fig. 69 – Status Summary Screen

3. Press the Configure button. Figure 70 shows

the Configuration screen.

Fig. 70 – Configuration Screen

4. Scroll through the listing on the Configure

menu to Flap Valve Configuration, and select

that line. See Fig. 71.

Fig. 71 – Flap Valve Configuration Screen

Two of the items on this screen can be

changed:

Controller ID -

This is the ID number of the flap valve

associated with this controller. (We will set

the ID number for the other controller in this

boiler in a moment.)

Number of controllers -

This is the total number of controllers

in the whole system. (For example, in a

system with four boilers, there will be eight

controllers.) See Table 14.

You need to set both of these values on the

Flap Valve Configuration screen for each

controller in the system.