System 2500 Operating & Installation Manual - Revision 07

5-5

operator has entered a THRESHOLD value which is greater than the value entered
for the Max Speed of the machine, which cannot be allowed. To clear this error
the operator must go to the MOTION DETECTOR choice of the Configure Menu
and enter the proper motion values.

069

PLS OUTPUT SPEED ADVANCE DATA INVALID, RE-ENTER IN
CONFIGURE MENU

1) The data stored to make the PLS Output Speed Advance feature work properly
is invalid. You must follow the instructions in this manual for programming
Output Speed Advance to correct this error (see Section 2.5.7).

092

MOTION NOT PRESENT WITHIN ALLOWED TIME AFTER AC RUN
SIGNAL APPLIED

1) Check to see if the machine is attempting to start, i.e., that power is being
applied to the clutch/brake solenoid valves so that they open briefly to engage
clutch. If not, check for trouble in clutch/brake drive circuit or in valves
themselves.

2) If machine is starting properly (valves actuate or brief motion takes place) but
this error causes machine to stop, check values programmed into MOTION
DETECTOR for motion threshold and clutch engagement time. See instructions
in this manual for setting up the MOTION DETECTOR and correct the stored
values if necessary.

3) Check for slippage of chain/sprocket drive for resolver unit and correct if
necessary.

093

MOTION ABSENT IN EXCESS OF ALLOWED TIME WITH AC RUN
SIGNAL PRESENT

1) Check value of maximum RPM for machine entered in MOTION DETECTOR
menu. Correct if necessary.

2) Check for slippage of chain/sprocket drive for resolver unit.

094

MOTION PRESENT WITHOUT AC RUN SIGNAL PRESENT

1) Verify that resolver cable round connector is securely installed to its mate on
rear of resolver package.