System 2500 Operating & Installation Manual - Revision 07

5-6

2) Verify that resolver cable is properly wired to 6-pin plug-in terminal strip for
Logic Unit.

3) Verify that 6-pin plug-in terminal strip is securely installed into header
(receptacle) on Logic Unit.

4) Check wiring of 'AC RUN' input on 20-terminal plug-in strip.

5) Verify that 20-terminal plug-in strip is securely installed into its header
(receptacle) on Logic Unit.

6) Check machine brake. Verify that braking time does not exceed 2 seconds.

7) Notify factory.

200

DIE-PROT SETUP DATA INVALID!
SETUP WILL BE LOST! PRESS 2,0,0, & CLEAR

The die protection data in the current setup has been found to be corrupt. When
the error is cleared there will be no DIE-PROT information in the current setup.
This means that the die protection inputs will not be programmed to respond
properly to the sensors that are present and therefore protection of the die cannot
be accomplished.

To clear this error the operator must be in the STOPS/FAULTS menu and this
error message must be on the display. Also, the mode selector keyswitch must be
in the PROG position. The operator must then press the 2, 0, and 0 keys in
sequence before pressing the CLEAR key. After clearing this error, Error 241 will
appear. The operator then has these options:

1) Go to the STORE/RECALL menu and recall a setup which has the correct PLS
and die protection data programmed for this die.

2) Manually enter new die protection information for the current setup.

202

DIE-PROT INPUT MODE INVALID

Bad data in memory has caused one of the die protection inputs to be programmed
so that the code for its die protection mode is not valid.

1) If this error is accompanied by Error 200, refer to the explanation above for
that error. Error 202 cannot be cleared if error 200 is present. If Error 200 is not