Mounting, 1 mounting the enclosure, 2 surface mounting – DMP Electronics XR2500F User Manual

Page 11: 3 flush mounting, 4 fire command center lcd keyboard, 5 metal backplate, Mounting the enclosure, Surface mounting, Flush mounting, Fire command center lcd keyboard

Advertising
background image

XR2500F Installation Guide

Digital Monitoring Products

3

IntRoduCtIon

Mounting

2.1 Mounting the Enclosure

The XR2500F must be mounted in a secure,

dry location to protect the unit from damage

due to tampering and the elements. The

enclosure can be either flush mounted or

surface mounted and includes a hinged door

with lock. The hole in the enclosure door

allows access to the Fire Command Center

without opening the door. Figure 1 illustrates

the mounting hole locations for the panel

enclosure.
The enclosure dimensions are 32” tall, 14.5”

wide, by 4” deep. The lid adds about 0.5” to

each side.

2.2 Surface Mounting

The enclosure center hole should be attached

to a wall stud. Due to the enclosure weight,

especially the batteries, it is extremely

important to mount the enclosure on the

stud. Attach the two holes beside the center

hole to sheetrock to secure enclosure. When

mounting the enclosure, be sure to leave

room for the panel door to swing open. The

door lock should be easily accessible.

2.3 Flush Mounting

The enclosure can also be flush mounted. Use

1” screws to secure the enclosure between

two studs using the two sets of holes on

the sides of the enclosure. Use the top and

bottom holes to secure to horizontal studs, if

necessary.

2.4 Fire Command Center LCD

Keyboard

A Fire Command Center LCD Keyboard

has been factory installed on the XR2500F

enclosure. A keyswitch has also been

installed and pre-wired to the left of the

keyboard. The user can turn the keyswitch to

enable the four function keys without opening

the enclosure door.

2.5 Metal Backplate

The XR2500F components are pre-wired

and installed on a metal backplate. The

backplate can be easily removed to keep components safe during pre-wire activities.
Remove AC and battery power from the XR2500F panel before removing the backplate. Disconnect all

battery, transformer, and the Fire Command Center LCD keyboard wires. From the panel, disconnect the AC

wires from terminals 1 and 2. Disconnect the battery wires either from the batteries or the panel terminals

3 and 4. Finally, disconnect the keyboard wires from panel terminals 7, 8, 9, and 10.
Remove the screws securing the backplate to the enclosure. Loosen the two top screws that the backplate

hangs on. After loosening and removing the screws, lift the backplate up slightly and pull the backplate

toward you. When reinstalling the backplate, be sure all connections are secure.
Figure 2 illustrates the backplate and the components. The backplate is shown in light gray.

3/4" X 1/2" Knockouts

Hole for Flush

Mounting

Holes for Surface Mounting

Holes for 1" screws for

Flush Mounting

Battery Shelf

Hole for Flush Mounting

Additional Holes for Surface Mounting

Figure 1: Mounting the XR2500F Enclosure

Advertising