Holdup alarm units ansi/ul 636, 1 ansi/ul 1610 required, 2 1100x wireless receiver – DMP Electronics XR2500F User Manual

Page 40: 3 wireless supervision time, 4 led display, 5 jamming detection, 6 local alarm, 7 message to transmit, 8 wireless audible annunciation option, 1 system trouble display

Advertising
background image

Digital Monitoring Products

XR2500F Installation Guide

32

CoMPlIanCe

Holdup Alarm Units

ANSI/UL 636

29.1 ANSI/UL 1610 Required

The programming and installation specifications contained in this section must be completed in addition to

ANSI/UL 1610 Specifications when installing a Model 1142 with a Model XR500 Series panel.

29.2 1100X Wireless Receiver

The Model 1100X Wireless Receiver in conjunction with the Model 1142 Holdup Alarm Transmitter must be

installed in the system.

29.3 Wireless Supervision Time

The Zone Information Supervision Time must be a maximum of 240 minutes.

29.4 LED Display

The LED Operation option display must be set to NO when using a Model 1142 Holdup Alarm Transmitter.

29.5 Jamming Detection

The Detect Wireless Jamming option must be set to YES.

29.6 Local Alarm

The Bell Action for a PN (Panic) type zone must be programmed as N (None).

29.7 Message to Transmit

The Armed Open and Armed Short messages for a PN (Panic) type zone must be programmed to A (Alarm).

29.8 Wireless Audible Annunciation Option

The Wireless Audible option must be selected as ANY for commercial applications.

Digital Burglar Alarm Communicator System Units

ANSI/ UL 1635

30.1 System Trouble Display

The Status List Display must include at least one keypad that displays system monitor troubles.

30.2 Digital Dialer Telephone Number

Both programmed telephone numbers must begin with a P.

30.3 Test Time

The Test Time option must be programmed so that the XR2500F sends a report once every 24 hours.

30.4 Closing Wait

The Closing Wait option must be programmed YES.

Police Station Connected and Local Burglar Alarm Units

ANSI/UL 365

31.1 System Trouble Display

The Status List Display must include at least one keypad that displays system monitor troubles.

31.2 Entry Delay

The maximum entry delay used must not be more than 60 seconds when using Model 350A or 350H Attack

housing.

31.3 Exit Delay

The maximum exit delay used must not be more than 60 seconds.