XR2500F Installation Guide

Digital Monitoring Products

41

WIRInG dIaGRaMs

39.3 Prewired 866 Class B Style W Modules with Multiple Notification Appliances

505-12 Power

Supply

J6

+ DC -

AC

Trouble

Batt

Trouble

J4

J3

J2

Green

LED

AC

AC

+ BAT -

Red
LED
DC

12 VDC @ 5 Amps

Battery

Start

The Auxiliary Power Supply and Notification Circuit
Module trouble contact zone must be programmed
as a Supervisory Type zone and must be selected
for display in the keypad status list.

Auxiliary Power Supply must be Listed for Fire
Protective Signaling Service. Power Supplies
must have battery backup.

Listed, Polarized

Notification Appliances

Model 308

10K EOL

Model 308

10K EOL

SM-12/24 Module

Sync module required when using
multiple notification appliances

When using a separate power supply, the
maximum current is 3 Amps.

See the Notification Appliance
section for a list of appliances.

The maximum voltage drop

between the panel Bell Output and

the Model 308 is 1 VDC when a

separate power supply is not used.

The Bell Output

programming for Fire

type zones must be set

to Steady

Model 310

1K EOL

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

Normal/Silence Switch

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

Normal/Silence Switch

DMP Model 866

45mA @ 12 VDC

The 866 Notification

Appliance Circuit

Module in alarm draws

up to 31mA through

its Terminal 3 Alarm

Input and 45mA from

its Terminal 1 Aux

Power Input.

See the 866

Installation (LT-0059)

Prewired to XR2500F panel

Note: If an

auxiliary power

supply is not used,

Terminals 3 and 4

jumper together to

supply Bell Power

from the panel

SM-12/24 Module