Two 866 nac modules, 1 description, 2 connection – DMP Electronics XR2500F User Manual

Page 15: 3 bell silence/bell trouble, Description, Connection, Bell silence/bell trouble, Introduction

Advertising
background image

XR2500F Installation Guide

Digital Monitoring Products

7

IntRoduCtIon

Two 866 NAC Modules

5.1 Description

Each 866 provides one style W indicating circuit for supervising listed polarized notification appliances,

such as bells, strobes, and horns. See Table 1: Notification Appliances for a list of approved notification

appliances.

5.2 Connection

Each 866 module is pre-installed on the removable backplate using the standard three-hole configuration.

The modules are factory pre-wired to each other and the XR2500F panel. Refer to the figure below and to

Figure 2: XR2500F System for wiring connections.
Connect a 12 or 24 VDC regulated, power limited power supply listed for Fire Protective Signaling Systems to

terminals 2 and 4 of each module to provide Notification appliance power. Connect notification appliances

to terminals 5 and 6 of each module. Each module provides a zone of notification and can be activated

separately.

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

866
Module #1

Normal/Silence Switch

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

866
Module #2

Normal/Silence Switch

To XR2500F Output #1 (J2 pin #2)

To XR2500F terminal 13 (Zone 1)

To XR2500F terminal 7
To 24 VDC Power Supply DC -
To XR2500F Output #2 (J2 pin #5)

To 24 VDC Power Supply DC +

To XR2500F terminal 15 (Zone 2)
To 24 VDC Power Supply

Listed, Polarized

Notification Appliances

See the Notification

Appliance section

Listed, Polarized

Notification Appliances

See the Notification

Appliance section

Pre-installed 1K EOL

Pre-installed 1K EOL

Figure 5: 866 Modules Wiring

5.3 Bell Silence/Bell Trouble

A bell silence switch on the 866 module is provided to prevent indicating devices from sounding during

system testing. When the Silence position is selected, a 15-second delay occurs before the 866 bell trouble

contacts (terminals 7 and 8) open. Select the Normal position after testing to return the 866 module to

normal operation.

Advertising