28.5 Proprietary Dialer

The Model XR2500F provides proprietary service when configured as a digital dialer.

28.6 DACT Central Station

DACT Central Station service can be provided under by adding an Ademco AB12M bell and bell housing.

28.7 Bell Cutoff

The Bell Cutoff time cannot be less than 15 minutes.

28.8 Standard or Encrypted Line Security

Standard Line Security is provided when configured as a Path 1 NET system using an XR500N panel. The NET

Check-in time must be set to 06 minutes or RDM. When programmed for Standard Line Security, Exit Time

Restart is disabled. When a dialer is required for 06 minute check-in time, an attack resistant enclosure

(DMP Model 350A) is required. When the check-in time is set to a number less than 200 seconds, an attack

resistant enclosure is not required.
To provide Encrypted Line security, install an XR500E panel.
For Encrypted Line security operation, communication between the Premise and Supervising Station provides

128 bit encryption when using an XR500E panel or an XR500 panel with an iCOM-E Encrypted Network Alarm

Router.
The Model XR500 Series Protected Premises Control Unit is suitable for Standard Line Security service when

configured for NET communication with SCS-1R receiving system. This configuration is approved for the

following:
AMCX - Central Station Alarm Units

APOU - Proprietary Alarm Units

28.9 Wireless Audible Annunciation Option

The Wireless Audible option must be selected as ANY for commercial applications.

28.10 Model 463G CELL Only, Standard or Encrypted Line Security

Standard or Encrypted Line Security is provided when programmed using CELL with no backup. XR500

cellular communication is used as primary with a 3 minute check-in when armed or disarmed.

Path 1 programming
Comm Type: = CELL

Checkin: = 3 minute

Path Type: = Primary

Fail Time: = 3 minute

Encrypt: = NO or YES*

Test Rpt: = NO

Sub Code: = NO or YES

*For Encrypted Line Security, program a Passphrase in Network Options.