J22 lx-bus expansion connector, 1 description, 2 lx-bus interface cards – DMP Electronics XR2500F User Manual

Page 34: 3 lx-bus leds, Ovc led, J21 serial connector, 2 serial connector leds

Advertising
background image

Digital Monitoring Products

XR2500F Installation Guide

26

InstallatIon

J22 LX-Bus Expansion Connector

20.1 Description

J22 LX-Bus and J21 RS-232 connectors cannot be used at the same time. Either use J21 to connect a serial

device for PC Log Reporting, or use J22 to connect an LX-Bus or Wireless device. This is determined by

where you install the jumper on J23 6-Pin Header. Reset the panel using J16 jumper to activate selected J23

operation. See the Connecting LX-Bus and Keypad Bus Devices section for maximum wiring distances.
Note: Do NOT use shielded wire when using the LX-Bus. Do NOT connect the wires from the 4-wire harness

to the panel terminals.

20.2 LX-Bus Interface Cards

Refer to the following tables to identify zone locations and numbers relative to J22 operation.

J22 LX-Bus Enabled

AND

One Interface Card

OR

461 Adaptor Card and

Multiple Interface

Cards

LX-Bus Zone Numbers

LX-Bus Zone Numbers

LX-Bus Zone Numbers

1

500-599

2

600-699

2 (A)

600-699

3 (B)

700-799

4 (C)

800-899

5 (D)

900-999

J22

LX-Bus

NOT

Enabled

One Interface Card

OR

461 Adaptor Card and

Multiple Interface

Cards

LX-Bus Zone Numbers

LX-Bus Zone Numbers

1

500-599

1 (A)

500-599

2 (B)

600-699

3 (C)

700-799

4 (D)

800-899

5 (E)

900-999

20.3 LX-Bus LEDs

The two LEDs, located near the bottom-right corner of J21 indicate data transmission and receipt. The

top LED flashes green to indicate the panel is transmitting LX-Bus data. The bottom LED flashes yellow to

indicate the panel is receiving LX-Bus data.

20.4. OVC LED

The Overcurrent LED (OVC) lights Red when the devices connected to the Keypad Bus and LX-Bus(es) draw

more current than the panel is rated for. The OVC is located above Outputs 1 and 2 on the panel and turns a

steady Red when lit. When the OVC LED lights Red, the LX-Bus(es) and keypad bus shut down.

J21 Serial Connector

21.1 Description

Note: J22 LX-Bus and J21 RS-232 connectors cannot be used at the same time. Either use J21 to connect a

serial device, or use J22 to connect an LX-Bus or Wireless device. This is determined by where you install

the jumper on the J23 6-Pin Header. Reset the panel using J16 jumper to activate selected J23 operation.

The maximum line impedance is 100 Ohms.
To enable J21 to operate in RS-232 mode place a jumper on the two pins next to the letter “R” on the J23

6-Pin header. The Serial Connector allows the XR2500F panel to transmit PC Log Reports directly to an

RS-232 device.

21.2 Serial Connector LEDs

The two LEDs, located near the bottom-right corner of J21 indicate data transmission and receipt. The

top LED flashes green to indicate the panel is transmitting serial data. The bottom LED flashes yellow to

indicate the panel is receiving serial data.

Advertising