XR2500F Installation Guide

Digital Monitoring Products

1

IntRoduCtIon

Introduction

1.1 Overview

The DMP XR2500F Addressable Fire Alarm Control Panel (FACP) is an expandable 24 VDC Fire Alarm Control

with built-in DACT and LCD Fire Command Center keyboard with membrane keyswitch. A complete system

can provide:
• 574 programmable inputs and outputs for commercial and industrial fire alarm service.
• Eight on-board grounded zones
• Two on-board 12 VDC Class B, Stye A powered zones
Connect a 12 or 24 VDC regulated, power limited power supply listed for Fire Protective Signaling Systems

to distribute notification appliance power between the two class B style W NAC outputs. Additional NAC

outputs can be added with conventional supervision modules or addressable power supply/boosters.

Addressable smoke detectors and input modules round out the XR2500F to deliver a truly flexible and

expansive fire detection and notification system. The Fire Alarm Control Panel is shipped pre-wired in a red

metal enclosure housing the necessary components to monitor and control fire alarm notification appliances.
The enclosure dimensions are as follows: 32” H x 14.5” W x 4” D. The lid adds about 0.5” to each side.

1.2 System Components

The XR2500F FACP consists of the following pre-wired components:
• One Model XR2500F Command Processor panel • One Model 893A Dual Phone Line module
• Two Model 866 Class B Style W NAC modules

• One Model 630F PCB and membrane switch

• One 16 VAC, 56 VA transformer

• Two Model 305 Plug-in Relays

• One Model 481 Zone Expansion Interface Card • One Metal Backplate

1.3 Power Specifications

Transformer Input: Primary input: 120 VAC, 60 Hz, Secondary output: 16 VAC 56 VA
Standby Battery:

12 VDC, 1.0 Amps Max. charging current

Auxiliary:

12 VDC output at 1.0 Amp Max*

Bell Output:

12 VDC at .7 Amp Max*

Note: The combined Auxiliary and Bell outputs total cannot exceed 1.9 Amps with a 56 VA Transformer.
All circuits are inherent Power Limited except the red battery wire and AC terminal.
* For Commercial Fire installations, see the Compliance Instructions section.

1.4 Communication

Built-in dialer or network communication to DMP Model SCS-1R Receivers
Built-in Contact ID communication to non-DMP receivers
893A Dual Phone Line Module with phone line supervision
Can operate as a local panel

1.5 Panel Zones

Eight 1k Ohm EOL burglary zones (zones 1 to 8). Connect to 869 Class A module for burglary applications.

Two 3.3k Ohm EOL powered zone with reset (zones 9 and 10).
Note: Use the supplied DMP Model 311 1k Ohm and DMP Model 301 3.3k Ohm resistors.

1.6 Keypad Bus

You can connect up to 15 of the following supervised keypads and expansion modules to the keypad bus:
• Alphanumeric Fire Command Centers or keypads
• Four- and/or single-zone expansion modules
• Single-zone detectors
• Access control modules