Area information, 1 ownership, 2 annunciation – DMP Electronics XR2500F User Manual

Page 37: 3 trouble display, 4 closing wait, 5 local bell supervision, Household burglar-alarm system unitsansi/ul 1023, 1 audible devices, 2 auxiliary circuits, 3 bell cutoff

Advertising
background image

XR2500F Installation Guide

Digital Monitoring Products

29

InstallatIon

Area Information

26.1 Ownership

The control unit system shall be under one ownership.

26.2 Annunciation

The System shall be installed so that when arming any area from any keypad, the local bell shall annunciate.

26.3 Trouble Display

The Status List programming shall be set to annunciate all trouble messages at all keypads.

26.4 Closing Wait

The Closing Wait option must be programmed YES.

26.5 Local Bell Supervision

When a local bell is employed, the power supply for the bell shall be under 24-hour protection. Proper

personnel for maintenance or security of the system shall be able to disarm that area.

Household Burglar-Alarm System Units

ANSI/UL 1023

27.1 Audible Devices

At least one listed audible device (Ademco AB12M) rated to operate over the voltage rate of 11.7 VDC to

12.8 VDC and rated at 85 DB minimum must be used.

27.2 Auxiliary Circuits

At least one burglary alarm initiating device shall be used on the system. If the voltage for the device is

applied by the control unit the burglary alarm initiating device shall be rated to operate over the range of

11.5 VDC to 12.7 VDC.

27.3 Bell Cutoff

The Bell Cutoff time cannot be less than five minutes.

27.4 Entry Delay

The maximum entry delay used must not be more than 45 seconds.

27.5 Exit Delay

The maximum exit delay used must not be more than 60 seconds.

27.6 Weekly Test

The product should be tested weekly.

27.7 Wireless Audible Annunciation Option

The Wireless Audible option must be selected as DAY for residential applications.

Central-Station and Proprietary Burglar-Alarm Units

ANSI/ UL 1610 AND ANSI/UL 1076

28.1 Opening/Closing Reports

The Opening/Closing Reports option must be programmed as YES. .

28.2 Closing Wait

The Closing Wait option must be programmed YES.

28.3 Entry Delay

The maximum entry delay used must not be more than 60 seconds.

28.4 Exit Delay

The maximum exit delay used must not be more than 60 seconds.