Bell output, 1 terminals 5 and 6, Keypad bus – DMP Electronics XR2500F User Manual

Page 28: 1 description, 2 terminal 7 - red, 3 terminal 8 - yellow, 4 terminal 9 - green, 5 terminal 10 - black, 6 j8 programming connection, 7 ovc led

Advertising
background image

Digital Monitoring Products

XR2500F Installation Guide

20

InstallatIon

Bell Output

12.1 Terminals 5 and 6

Terminal 5 supplies positive 12 VDC regulated power for alarm bells or horns. This output can be steady,

pulsed, or temporal depending upon the Bell Action specified in Output Options. Terminal 6 is the ground

reference for the bell circuit. This supervised output detects 10k Ohms or less as normal. The indicating

appliance can supply this resistance. If using a horn or siren, a 1k Ohm 1/2 W EOL resistor (provided) should

be added across the bell circuit to provide supervision. See the Notification Appliance section for a list of

approved notification appliances and the Wiring Diagrams for connections.

Keypad Bus

13.1 Description

XR2500F panel terminals 7, 8, 9, and 10 are for the keypad bus. In addition to Fire Command Centers and

Remote Fire Command Centers, you can connect up to fifteen supervised keypads and multiple unsupervised

keypads to the XR2500F. In addition to Security Command keypads, you can also connect any combination

of zone expansion modules, 5845LX Glassbreak detectors, and 6155LX PIRs to the data bus. Refer to the

specific device Installation sheet for the maximum number of keypad Bus devices.
Refer to the section titled LX-Bus for complete information about the LX-Bus 4-pin header and expansion

slot.
Note: Do not use shielded wire for LX-Bus/Keypad Bus circuits.

13.2 Terminal 7 - RED

This terminal supplies positive 12 VDC regulated to power Fire Command Centers and zone expansion

modules. Terminal 7 also supplies power for any auxiliary device. The ground reference for terminal 7 is

terminal 10.
The output current is shared with the smoke power output on terminal 11 and Zones 9 and 10. Current draw

for all connected devices must not exceed the panel maximum current rating. See Power Supply in the

Compliance section for maximum current in a fire listed application.

13.3 Terminal 8 - YELLOW

Terminal 8 receives data from keypads and zone expansion modules. It cannot be used for any other

purpose.

13.4 Terminal 9 - GREEN

Terminal 9 transmits data to keypads and zone expansion modules. It cannot be used for any other purpose.

13.5 Terminal 10 - BLACK

Terminal 10 is the ground reference for Fire Command Centers, zone expansion modules, and all auxiliary

devices being powered by terminal 7.

13.6 J8 Programming Connection

A 4-pin header (J8) is provided to connect a keypad when using a DMP Model 330 Programming Cable. This

provides a quick and easy connection for panel programming.
You may also use the J8 Programming Header to connect Keypad Bus devices. This is an alternative to

connecting keypad bus devices to terminals 7, 8, 9, and 10.

13.7 OVC LED

The Overcurrent LED (OVC) lights Red when the devices connected to the Keypad Bus and LX-Bus(es) draw

more current than the panel is rated for. The OVC is located above Outputs 1 and 2 on the panel and turns a

steady Red when lit. When the OVC LED lights Red, the LX-Bus(es) and Keypad bus are shut down.