XR2500F Installation Guide

40

CoMPlIanCe

Wiring Diagrams

39.1 Prewired 866 Modules with NAC Extender

Model 310

1K EOL

Model 310

1K EOL

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

Normal/Silence Switch

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

Normal/Silence Switch

DMP Model 866

45mA @ 12 VDC

The 866 Notification

Appliance Circuit

Module in alarm draws

up to 31mA through

its Terminal 3 Alarm

Input and 45mA from

its Terminal 1 Aux

Power Input.

See the 866

Installation (LT-0059)

The Bell Output programming for Fire type zones must be set to Steady

Prewired to XR2500F panel

PowerPath NAC Extender

Models

PS-8

PS-8E

PS-6

PS-6E

See PowerPath installation for

detailed connection

instructions

Note: Terminals 3
and 4 jumper together
to supply Bell Power
from the panel

39.2 Prewired 866 Class B Style W Modules using Single Notification Appliance

Model 308

10K EOL

Model 308

10K EOL

Listed, Polarized

Notification Appliance
See the Notification

Appliance section for a

list of appliances.

The maximum

voltage drop

between the panel

Bell Output and the

Model 308 EOL is 1

VDC when a

separate power

supply is not used.

The Bell Output programming for Fire type zones must be set to Temporal.

Only one notification appliance may be used when not using a sync module.

Model 310

1K EOL

Model 310

1K EOL

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

Normal/Silence Switch

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

Normal/Silence Switch

DMP Model 866

45mA @ 12 VDC

The 866 Notification

Appliance Circuit

Module in alarm draws

up to 31mA through

its Terminal 3 Alarm

Input and 45mA from

its Terminal 1 Aux

Power Input.

See the 866

Installation (LT-0059)

Prewired to XR2500F panel

Note: Terminals 3
and 4 jumper together
to supply Bell Power
from the panel