CoMPlIanCe

California State Fire Marshal Specifications

37.1 Bell Output Definition

The Model XR2500F panel Bell Output must be programmed to operate steady on burglary alarms and pulsed,

temporal, or California School Code on fire alarms.

New York City (MEA) Specifications

38.1 Introduction

The programming and installation specifications contained in this section must be completed when installing

the XR500 Series panel for New York City (MEA) fire alarm installations that provide a digital dialer with

network IP communication as backup. Fire alarm installations that use two digital dialer telephone lines do

not need to comply with these specifications.

38.2 Digital Dialer and Network Communication

When used with a central office communicator or a transmitter, the installation and operation of the

equipment and devices shall comply with 3RCNY 17-01. The installation shall employ the digital dialer as

the primary communicator (using telephone line) with network IP communication as backup or secondary

means of communication. It shall have the capability of transmitting separate and distinct signals to

indicate manual pull station alarm, automatic detection alarm, sprinkler waterflow alarm, supervisory signal

indications and trouble indications.

38.3 Wiring

All wiring must be in accordance with NEC, ANSI, and NFPA 70. All network cabling must be installed in

accordance with NFPA 70 for communication circuits.

38.4 Communication Programming

For digital dialer communication with supervised network backup, program the following:

PRIMARY COMM TYPE = DD

FIRST PHONE NUMBER = Central Station Receiver Phone Number

BACKUP COMM TYPE = NET

RECEIVER

ALARMS = YES

38.5 Additional Requirements

Program and install the equipment to comply with NFPA basic fire requirements. Refer to the Universal Fire

Alarm Specifications and ANSI/UL 864, NFPA 72 in this document.