Fire command center, 1 description, 2 connection – DMP Electronics XR2500F User Manual

Page 19: 3 remote fire command center, Description, Connection, Remote fire command center, Introduction

Advertising
background image

XR2500F Installation Guide

Digital Monitoring Products

11

IntRoduCtIon

Fire Command Center

8.1 Description

The XR2500F provides an LCD display and 20-key keyboard for programming and system user operation. The

Fire Command Center is installed on the XR2500F enclosure door. A keyswitch is installed and pre-wired

to the left of the keyboard. The user must turn the keyswitch to enable the four function keys. See the

illustration below.

POWER

TROUBLE

ALARM

COMMAND

1

2

3

4

5

6

7

8

9

0

ABC

DEF

GHI

JKL

MNO

PQR

STU

VWX

YX

ENABLE

SILENCE

RESET

TEST

DRILL

Fire Command Center

Figure 10: Fire Command Center LCD and Keyboard

8.2 Connection

The display and keyboard are factory pre-wired to the XR2500F panel terminals 7, 8, 9, and 10. For standby

battery calculations, the display draws 92mA of current in normal standby or alarm condition. See Panel

Standby Battery Calculations. The keyswitch is pre-wired to the membrane keyboard.

8.3 Remote Fire Command Center

Up to fifteen Model 630F Remote Fire Command Centers may be remotely attached to the XR2500F system.

See the 630F Installation Guide (LT-0741) for additional information.