XR2500F Installation Guide

Digital Monitoring Products

33

CoMPlIanCe

31.4 Bell

A local audible signal appliance must be used such as Ademco AB12M bell and bell housing.
The alarm housing for a mercantile alarm system without a remote alarm transmission connection shall be

mounted on the outside of the building, visible from a public street or highway. It shall be accessible for

examination and repair. It shall also be located not more than four stories above the street level unless:
a) A second alarm sounding device and housing, intended for outside service, is mounted adjacent to the

premises or area of the building in which the alarm system is installed or
b) A second alarm sounding device, intended for inside service, is mounted within the premises.
In either case, the outside alarm sounding device and housing may be mounted as high as the seventh floor.

31.5 Bell Cutoff

The Bell Cutoff time cannot be less than 15 minutes.

31.6 Automatic Bell Test

The Automatic Bell Test option must be programmed as YES.

31.7 Standard or Encrypted Line Security

Standard Line Security is provided when configured as a Path 1 NET system using an XR500N panel or an

XR500 panel with an iCOM™ Network Alarm Router. The NET Check-in time must be set to 06 minutes or

RDM. When programmed for Standard Line Security, Exit Time Restart is disabled. When a dialer is required

for 06 minute check-in time, an attack resistant enclosure (DMP Model 350A) is required. When the check-in

time is set to a number less than 200 seconds, an attack resistant enclosure is not required.
To provide Encrypted Line security, install an XR500E panel or an XR500 panel with an iCOM-E™ Encrypted

Network Alarm Router.
For Encrypted Line security operation, communication between the Premise and Supervising Station provides

128 bit encryption when using an XR500E panel or an XR500 panel with an iCOM-E Encrypted Network Alarm

Router.

31.8 Wireless Audible Annunciation Option

The Wireless Audible option must be selected as ANY for commercial applications.

31.9 Model 463G CELL Only, Standard or Encrypted Line Security

Standard or Encrypted Line Security is provided when programmed using CELL with no backup. XR500

cellular communication is used as primary with a 3 minute check-in when armed or disarmed.

Path 1 programming
Comm Type: = CELL

Checkin: = 3 minute

Path Type: = Primary

Fail Time: = 3 minute

Encrypt: = NO or YES*

Test Rpt: = NO

Sub Code: = NO or YES

*For Encrypted Line Security, program a Passphrase in Network Options.