3 cable length and number of devices requirements – Flowserve MX FOUNDATION Fieldbus Field Unit User Manual

Page 21

Advertising
background image

21

MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11

flowserve.com

2.6.2.2 Network Cable Connections to Other Network Components

Each FOUNDATION fieldbus network may require some or all of the following components depending
on the application:

• Junction Box/Terminal Blocks
• Connectors
• Power Supplies
• Power Conditioners
• Terminators
• Intrinsic Safety Barriers
• Bridge and Repeaters

For cable connecting information on these components, see the following:

• FOUNDATION Fieldbus Wiring and Installation 31.25 kbits/s, Voltage Mode, Wire Medium AG-140
• Relcom Inc. Fieldbus Wiring Design and Installation Guide
• ANSI/ISA-S50.02, Part 2-1992, Fieldbus Standard for Use in Industrial Control Systems Part 2:

Physical Layer Specification and Service Definition

2.6.2.3 Cable Length and Number of Devices Requirements

The network cable consists of a trunk, segments, and spurs. The trunk is the main connection
between all the devices. A segment is a section of the cable that contains the terminators. A spur
connects to the trunk through a junction box. The following topologies are possible:

• Point-to-point
• Bus with Spurs
• Daisy Chain
• Tree topology
• Combination of the above

Figure 2.15 – Network with Spurs

T

Fieldbus

I/O

Control Highway

DCS

(Host)

Terminator

Junction

Box

Fieldbus Trunk

Spur

Spur

T

Terminator

MX/QX FF

Actuator

MX/QX FF

Actuator

MX/QX FF

Actuator

MX/QX FF

Actuator