Flowserve MX FOUNDATION Fieldbus Field Unit User Manual

Page 58

Advertising
background image

MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11

58

Transducer Block Parameters

Description

Bit 09 PB PA Board Present

Bit 10 CSE Chosen for Input

Bit 11 DeviceNet Board Present

Bit 12 Phase Lost – Indicates field unit has noticed a phase(s) is absent

for the three-phase power. Value of 1=True, Value of 0=False.

Bit 13 Phase Reverse – Indicates field unit has noticed a 3-phase

rotation is incorrect. The field unit will operate the actuator in the proper

direction to prevent damage to the valve. Value of 1=True, Value of

0=False.

Bit 14 Not Used

Bit PB DP Board Present

TQ_STATUS

Torque Information. Details are given for the Reference and the Last

torque, expressed as reference percentages of the rated torque (stated

on the nameplate) that occurred at Breakout, Ending, and Peak Running

for both the opening and closing directions. Torque will be expressed

proportionally as a reference only from 40-100% inclusive. Initial

indication may read 0% until torque exceeds 40% minimum.

Subparameter 0

uint16_var

Unused.

Subparameter 1

uint16_var

Average Last Close torque.

Subparameter 2

uint16_var

Average Last Open torque.

Subparameter 3

uint16_var

Last Peak Opening torque.

Subparameter 4

uint16_var

Last Breakout Open torque - the last starting value.to open torque

Subparameter 5

uint16_var

Last Breakout Close torque - the last starting to close torque value.

Subparameter 6

uint16_var

Last Ending Open torque - the last torque value during opening.

Subparameter 7

uint16_var

Peak Ref. Open torque - the peak reference opening torque value, a

saved value.

Subparameter 8

uint16_var

Peak Open torque - the peak torque when opening.

Subparameter 9

uint16_var

Last Ending Close - the last torque value when going closed.

Subparameter 10

uint16_var

Breakout Ref. Open torque - the reference starting to open torque value,

a saved value.

Subparameter 11

uint16_var

Breakout Ref. Close torque - the reference starting to close torque

value, a saved value

Subparameter 12

uint16_var

Ending Ref. Open torque - the reference last torque value during

opening, a saved value

Subparameter 13

uint16_var

Update Ending Ref. Close torque - update the reference ending torque

value when going closed, a saved value

Subparameter 14

uint16_var

Update Peak Ref. Close torque - update the peak reference closing

torque value, a saved value

TP_STATUS

Torque Profile Information

Advertising