MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11

flowserve.com

Transducer Block Parameters

Description

Subparameter R3_FUNCTION

Function assigned to the relay.

Subparameter

R3_CONTACT_TYPE

User configurable realy contact type. Value 1=Close, 2=Open
and 4=Blinker.

Subparameter R3_POSITION

The relay gets energized when the actuator moves the valve to
this user configurable position.

Subparameter R4_FUNCTION

Function assigned to the relay.

Subparameter

R4_CONTACT_TYPE

User configurable realy contact type. Value 1=Close, 2=Open
and 4=Blinker.

Subparameter R4_POSITION

The relay gets energized when the actuator moves the valve to
this user configurable position.

Subparameter RM_SETTINGS

The monitor relay indicates the actuator is available for remote
operation.

Bit 00 to Bit 02 Not used

Bit 03 ESD signal

Bit 04 Inhibit signal

Bit 05 Over torque

Bit 06 Local stop/off

Bit 07 Local selected

OPT_DIGITAL_OUTPUT_RELAYS

Configuration for R5, R6, R7 and R8 relays on optional digital
output relay board.

Subparameter ENABLED

Digital output relays enabled status. Value 0=Disabled and
1=Enabled.

Subparameter STATUS

Contact operation status.

Bit 00 to Bit 03 Not used

Bit 04 R8 contacts status

Bit 05 R7 contacts status

Bit 06 R6 contacts status

Bit 07 R5 contacts status

Subparameter R5_FUNCTION

Function assigned to the relay.

Subparameter

R5_CONTACT_TYPE

User configurable realy contact type. Value 1=Close, 2=Open
and 4=Blinker.

Subparameter R5_POSITION

The relay gets energized when the actuator moves the valve to
this user configurable position.

Subparameter R6_FUNCTION

Function assigned to the relay.

Subparameter

R6_CONTACT_TYPE

User configurable realy contact type. Value 1=Close, 2=Open
and 4=Blinker.

Subparameter R6_POSITION

The relay gets energized when the actuator moves the valve to
this user configurable position.