Channel 2 – Position and Bus Mode
The channel 2 Discrete Input function block, DI_POSITION_AND_BUS_MODE_CHAN, makes actuator
status information available to other function blocks. The status information describes the position of
the actuator, that is open or closed, the direction of motion of the actuator, that is opening or closing,
and the operating mode, that is either Local, Remote, or Stop (off).
Channel 2
DI_POSITION_AND_BUS_MODE_CHAN
Value
Opened + Remote
0x21
Closed + Remote
0x22
Opening + Remote
0x24
Closing + Remote
0x28
Stop + Remote
0x30
Opened + Local
0x41
Closed + Local
0x42
Opening + Local
0x44
Closing + Local
0x48
Stop + Local
0x50
Opened + Stop
0x81
Closed + Stop
0x82
Opening + Stop
0x84
Closing + Stop
0x88
Stop + Stop
0x90
Channel 3 – Position Channel
The Channel 3 Discrete Input function block, DI_POSITION_CHAN, makes actuator status informa-
tion available to other function blocks. The status information describes the position or direction of
motion of the actuator, that is either Opened, Closed, Opening, Closing, or Stop.
Channel 3
DI_POSITION_CHAN
Value
Opened
0x01
Closed
0x02
Opening
0x04
Closing
0x08
Stop
0x10
Channel 4 – Actuator Faults 1
The Channel 4 Discrete Input function block, DI_ACTUATOR_FAULTS_1_CHAN, makes actuator faults
available to other function blocks. The reported faults include:
• Valve jammed in motion due to a tripped torque switch
• Valve was manually moved with the actuator handwheel
• An over torque condition while traveling
• Loss of electrical phase
• Thermal overload indicating the motor has overheated and the thermistor has opened.