Channel 2 – position and bus mode, Channel 3 – position channel, Channel 4 – actuator faults 1 – Flowserve MX FOUNDATION Fieldbus Field Unit User Manual

Page 46

Advertising
background image

MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11

46

Channel 2 – Position and Bus Mode

The channel 2 Discrete Input function block, DI_POSITION_AND_BUS_MODE_CHAN, makes actuator
status information available to other function blocks. The status information describes the position of
the actuator, that is open or closed, the direction of motion of the actuator, that is opening or closing,
and the operating mode, that is either Local, Remote, or Stop (off).

Channel 2

DI_POSITION_AND_BUS_MODE_CHAN

Value

Opened + Remote

0x21

Closed + Remote

0x22

Opening + Remote

0x24

Closing + Remote

0x28

Stop + Remote

0x30

Opened + Local

0x41

Closed + Local

0x42

Opening + Local

0x44

Closing + Local

0x48

Stop + Local

0x50

Opened + Stop

0x81

Closed + Stop

0x82

Opening + Stop

0x84

Closing + Stop

0x88

Stop + Stop

0x90

Channel 3 – Position Channel

The Channel 3 Discrete Input function block, DI_POSITION_CHAN, makes actuator status informa-
tion available to other function blocks. The status information describes the position or direction of
motion of the actuator, that is either Opened, Closed, Opening, Closing, or Stop.

Channel 3

DI_POSITION_CHAN

Value

Opened

0x01

Closed

0x02

Opening

0x04

Closing

0x08

Stop

0x10

Channel 4 – Actuator Faults 1

The Channel 4 Discrete Input function block, DI_ACTUATOR_FAULTS_1_CHAN, makes actuator faults
available to other function blocks. The reported faults include:

• Valve jammed in motion due to a tripped torque switch
• Valve was manually moved with the actuator handwheel
• An over torque condition while traveling
• Loss of electrical phase
• Thermal overload indicating the motor has overheated and the thermistor has opened.