48

Channel 6 – Actuator Alarms

The Channel 6 Discrete Input function block, DI_ACTUATOR_ALARMS_CHAN, makes actuator alarms
available to other function blocks. The alarms include:

• Local emergency shut down has occurred; the field unit will command the actuator to go to a

preconfigured position, or stop, or ignore the ESD.

• Remote emergency shut down has been received from the network host; the field unit will

command the actuator to go to a preconfigured position, or stop, or ignore the ESD.

• Open inhibit is active.
• Close inhibit is active.

Channel 6

DI_ACTUATOR_ALARMS_CHAN

Value

Local ESD Active

0x01

Remote ESD Active

0x02

Open Inhibit Active

0x04

Close Inhibit Active

0x08

Local ESD Active + Open Inhibit

0x05

Local ESD Active + Close Inhibit

0x09

Remote ESD Active + Open Inhibit

0x06

Remote ESD Active + Close Inhibit

0x0A

Open Inhibit Active + Close Inhibit Active

0x0C

Channel 7 - Discrete User Input

The Channel 7 Discrete Input function block, DI_DISC_USER_INPUT_CHAN, makes general-purpose
contact inputs available to other function blocks. The functions in the table, such as ESD, must
be configured to the OFF state locally in the MX/QX FF setup menus in order to use the inputs as
general-purpose inputs. Functions, such as ESD, when configured to OFF, are not enabled. Refer to
the following sections in Installation and Operation Manual Bulletins LMENIM2306 for the MX and
LMENIM3306 for the QX:

• Section 4.17 – ESD - Emergency Shutdown
• Section 4.17.2 – Inhibits - Open/Close Inhibit
• Section 4.13 – Remote Control - Open/Close/Stop Pushbutton Inputs This channel places each

discrete input to 0 if the discrete input is not enabled.

Channel 7 DI_DISC_USER_INPUT_

CHAN

Terminal #

Function

Value

User input number 0

30

ESD Input (default)

Bit 0

User input number 1

34

Open Inhibit (default)

Bit 1

User input number 2

35

Close Inhibit (default)

Bit 2

Remote Stop Input

26

Stop Pushbutton Input

Bit 3

Remote Open Input

25

Open Pushbutton Input

Bit 4

Remote Close Input

27

Close Pushbutton Input

Bit 5