Channel 5 – actuator faults 2 – Flowserve MX FOUNDATION Fieldbus Field Unit User Manual

Page 47

Advertising
background image

47

MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11

flowserve.com

Channel 4

DI_ACTUATOR_FAULTS_1_CHAN

Value

Monitor Relay

0x01

Valve Jammed

0x02

Manual Moved

0x04

Over Torque

0x08

Phase Error

0x10

Over Temp

0x20

Monitor Relay + Valve Jammed

0x03

Monitor Relay + Manual Move

0x05

Monitor Relay + Over Torque

0x09

Monitor Relay + Phase Error

0x11

Monitor Relay + Over Temp

0x21

Monitor Relay + Valve Jammed + Manual Move

0x07

Monitor Relay + Valve Jammed + Phase Error

0x13

Monitor Relay + Valve Jammed + Over Temp

0x23

Channel 5 – Actuator Faults 2

The Channel 5 Discrete Input function block, DI_ACTUATOR_FAULTS_2_CHAN, makes actuator faults
available to other function blocks. The reported faults include:

• Valve jammed in motion due to a tripped torque switch
• Valve was manually moved with the actuator handwheel
• An over torque condition occurred while traveling in the open direction
• An over torque condition occurred while traveling in the close direction
• Loss of electrical phase at the motor
• Thermal overload indicating the motor has overheated and the thermistor has opened; time is

required for the motor to cool and reset the thermistor.

Channel 5

DI_ACTUATOR_FAULTS_2_CHAN

Value

Thermal Overload

0x01

Phase Error

0x02

Valve Jammed

0x04

Manual Moved

0x08

Open Torque Switch Fault

0x10

Close Torque Switch Fault

0x20

Thermal Overload + Manual Moved

0x09

Thermal Overload + Phase Error

0x03

Thermal Overload + Valve Jammed

0x05

Open Torque Switch Fault + Manual Moved

0x18

Close Torque Switch Fault + Manual Moved

0x28