MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11

62

Transducer Block Parameters

Description

Bit 13 Pair # 13 (D13/Q13) of wheel 4 fault

Bit 14 Pair # 14 (D14/Q14) of wheel 4 fault

Bit 15 Pair # 15 (D15/Q15) of wheel 5 fault

Bit 16 Pair # 16 (D16/Q16) of wheel 5 fault

Bit 17 Pair # 17 (D17/Q17) of wheel 5 fault

Bit 18 Pair # 18 (D18/Q18) of wheel 6 fault

Bit 19 Pair # 19 (D19/Q19) of wheel 6 fault

Bit 20 Pair # 20 (D20/Q20) of wheel 6 fault

Bit 21 Pair # 21 (D21/Q21) of wheel 7 fault

Bit 22 Pair # 22 (D22/Q22) of wheel 7 fault

Bit 23 Pair # 23 (D23/Q23) of wheel 7 fault

Bit 24 Pair # 24 (D24/Q24) of wheel 8 fault

Bit 25 Pair # 25 (D25/Q25) of wheel 8 fault

Bit 26 Pair # 26 (D26/Q26) of wheel 8 fault

Bit 27 Pair # 27 (D27/Q27) of wheel 9 fault

Bit 28 Pair # 28 (D28/Q28) of wheel 9 fault

Bit 29 Pair # 29 (D29/Q29) of wheel 9 fault

Bit 30 and Bit 31 Not used

SOURCE_OF_LIMIGARD

The bit enumerated parameter provides LimiGard™ source of
failure information. Bit value 1 indicates the active source of
Limigard.

Bit 00 Not used

Bit 01 CCW & ENABLE asserted but CCW contactor not present

Bit 02 CW & ENABLE asserted but CW contactor not present

Bit 03 ENABLE not asserted but relay contact closed in error

Bit 04 ENABLE not asserted but relay drive transistor asserted
in error

Bit 05 ENABLE asserted but relay contact not closed

Bit 06 ENABLE asserted but relay drive transistor failed

Bit 07 CCW not asserted but relay contact closed in error

Bit 08 CCW not asserted but relay drive transistor asserted in
error

Bit 09 CCW asserted but relay contact not closed

Bit 10 CCW asserted but relay drive transistor failed

Bit 11 CW not asserted but relay contact closed in error