2 view settings, 3 checking the normal display – Flowserve MX FOUNDATION Fieldbus Field Unit User Manual

Page 26

Advertising
background image

MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11

26

2.9.2 View Settings

Refer to Installation and Operation Manual Bulletins LMENIM2306, for the MX and LMENIM3306 for
the QX to access the view settings menu. Verify the settings as follows:

1. From the VIEW SETTINGS display, scan to the VIEW FF? display

2. From VIEW FF? display, select YES and check that the FF status is ON. This confirms that FF is

enabled.

3. If the MX/QX contacts are to be controlled via the network to control external equipment, from

the VIEW FF? display, select NO and obtain the VIEW STATUS AND ALARM CONTROL? display.
Verify that the digital outputs, S1a, S1b, S2a, S2b are set for “Network” controlled.

2.9.3 Checking the Normal Display

Place the selector switch in LOCAL or REMOTE position. The valve position will be indicated at the
top of the LCD. STATUS OK or FF COMM LOSS should be indicated at the bottom of the LCD display.

• If STATUS OK is displayed, then the field device is communicating with the LAS.
• If FF COMM LOSS is displayed, no communication is occurring. This could be due to a number

of factors, including problems with the Host/Master station and/or the network. Check all local
connections and configurations. If these are correct and the FF COMM LOSS is still displayed, then
the solution to this problem must await full system commissioning.

Figure 2.17 – Normal Display

Remote

Local

or

Remote

Field unit is communicating

with host/master station

Bus power and

no communication

No bus power

Local

or

Remote

Local

or

100% OPEN

STATUS OK

100% OPEN

100% OPEN

FF COMM LOSS

HARDWARE FAILURE

Advertising