Flowserve MX FOUNDATION Fieldbus Field Unit User Manual

Page 66

Advertising
background image

MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11

66

Transducer Block Parameters

Description

Subparameter POLARITY

Analog-1 output polarity configuration. Value 1=High value at
open/max and 2=High value at close/min.

Subparameter ATT_SCALE

ATT scaling when analog-1 output function configured as ATT.

Subparameter VALUE

Analog-1 output value. Range: 0 to 100%.

ANALOG_2_OUTPUT

Record provides support for configuration of analog-2 output
board.

Subparameter STATUS

On/off status of the analog-2 output board. Value 1=On and
2=Off.

Subparameter FUNCTION

Analog-2 output function configuration. Value 1=APT and
2=ATT.

Subparameter OFFSET

Analog-2 output type, value and range configuration. Value
1=4-20mA, 2=0-20mA, 4=1-5V, 8=0-5V, 16=2-10V and
32=0-10V.

Subparameter POLARITY

Analog-2 output polarity configuration. Value 1=High value at
open/max and 2=High value at close/min.

Subparameter ATT_SCALE

ATT scaling when analog-2 output function configured as ATT.

Subparameter VALUE

Analog-2 output value. Range: 0 to 100%.

STD_DIGITAL_OUTPUT_RELAYS

Configuration for R1, R2, R3 and R4 relays on standard digital
output relay board.

Subparameter ENABLED

Digital output relays enabled status. Value 0=Disabled and
1=Enabled.

Subparameter STATUS

Contact operation status.

Bit 00 to Bit 02 Not used

Bit 03 RM contact status

Bit 04 R4 contacts status

Bit 05 R3 contacts status

Bit 06 R2 contacts status

Bit 07 R1 contacts status

Subparameter R1_FUNCTION

Function assigned to the relay.

Subparameter

R1_CONTACT_TYPE

User configurable realy contact type. Value 1=Close, 2=Open
and 4=Blinker.

Subparameter R1_POSITION

The relay gets energized when the actuator moves the valve to
this user configurable position.

Subparameter R2_FUNCTION

Function assigned to the relay.

Subparameter

R2_CONTACT_TYPE

User configurable realy contact type. Value 1=Close, 2=Open
and 4=Blinker.

Subparameter R2_POSITION

The relay gets energized when the actuator moves the valve to
this user configurable position.