Flowserve MX FOUNDATION Fieldbus Field Unit User Manual
Page 57
57
MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11
flowserve.com
Transducer Block Parameters
Description
Bit 07 Not Used
Bit 08 User Input O/default = ESD Input – User Input 0. Referenced as
Terminal 30. Connect with 120 VAC or 24 VDC. Minimum ON voltage
19.2 VAC/DC; maximum OFF voltage 5 VAC/DC. Value of 1=True/
ON, Value of 0=False/OFF. Emergency shutdown input. ESD must be
configured for OFF to use as a basic user input.
Bit 09 User Input 1/default = Open Inhibit Input – User Input 1.
Referenced as Terminal 34. Connect with 120 VAC or 24 VDC. Minimum
ON voltage 19.2 VAC/DC; maximum OFF voltage 5 VAC/DC. Value of
1=True/ON, Value of 0=False/OFF. Open inhibit input. Open inhibit must
be configured for OFF to use as a basic user input.
Bit 10 User Input 2/default = Close Inhibit Input – User Input 2.
Referenced as Terminal 35. Connect with 120 VAC or 24 VDC. Minimum
ON voltage 19.2 VAC/DC; maximum OFF voltage 5 VAC/DC. Value of
1=True/ON, Value of 0=False/OFF. Close inhibit input. Close inhibit must
be configured for OFF to use as a basic user input.
Bit 11 3/Remote Stop Input – User Input 3. Referenced as Terminal 26.
Connect with 120 VAC or 24 VDC. Minimum ON voltage 19.2 VAC/DC;
maximum OFF voltage 5 VAC/DC. Value of 1=True/ON, Value of 0=False/
OFF. Remote stop input. Remote Control must be configured for OFF to
use as a basic user input.
Bit 12 4/Remote Open Input – User Input 4. Referenced as Terminal
25. Connect with 120 VAC or 24 VDC. Minimum ON voltage 19.2 VAC/
DC; maximum OFF voltage 5 V AC/DC. Value of 1=True/ON, Value of
0=False/OFF. Remote open input. Remote Control must be configured
for OFF to use as a basic user input.
Bit 13 User Input 5/Remote Close Input – User Input 5. Referenced as
Terminal 27. Connect with 120 VAC or 24 VDC. Minimum ON voltage
19.2 VAC/DC; maximum OFF voltage 5 VAC/DC. Value of 1=True/ON,
Value of 0=False/OFF. Remote close input. Remote Control must be
configured for OFF to use as a basic user input.
Subparameter 5 uint16_var
DigitalInput_2. read only 16-bit unsigned value. Contains field unit
status and digital input status.
Bit 00 Analog Board 1 Present
Bit 01 Analog Board 2 Present
Bit 02 Analog Input 1 Lost – Indicates analog Input 1 is not receiving a
4-20 mA signal. Referenced as terminals 39 and 28 (common). Value of
1=True, Value of 0=False.
Bit 03 Analog Input 2 Lost – Indicates analog Input 2 is not receiving a
4-20 mA signal. Referenced as terminals 40 and 28 (common). Value of
1=True, Value of 0=False.
Bit 04 Undefined
Bit 05 Not Used
Bit 06 DDC Board Present – Indicates presence of optional MX/QX DDC
board. This board allows the actuator to be configured for use on the
Fieldbus network. Value of 1=True, Value of 0=False.
Bit 07 I/O Optional Board Present – Indicates presence of optional
I/O board. This board provides AR-1 to AR-3 Relays and User Inputs
6-8. This board also contains the 4-20 mA outputs for analog position
transmitter (APT) and analog torque transmitter (ATT). Value of 1=True,
Value of 0=False.
Bit 08 FF Board Present