MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11

flowserve.com

Transducer Block Parameters

Description

Bit 07 Not Used

Bit 08 User Input O/default = ESD Input – User Input 0. Referenced as

Terminal 30. Connect with 120 VAC or 24 VDC. Minimum ON voltage

19.2 VAC/DC; maximum OFF voltage 5 VAC/DC. Value of 1=True/

ON, Value of 0=False/OFF. Emergency shutdown input. ESD must be

configured for OFF to use as a basic user input.

Bit 09 User Input 1/default = Open Inhibit Input – User Input 1.

Referenced as Terminal 34. Connect with 120 VAC or 24 VDC. Minimum

ON voltage 19.2 VAC/DC; maximum OFF voltage 5 VAC/DC. Value of

1=True/ON, Value of 0=False/OFF. Open inhibit input. Open inhibit must

be configured for OFF to use as a basic user input.

Bit 10 User Input 2/default = Close Inhibit Input – User Input 2.

Referenced as Terminal 35. Connect with 120 VAC or 24 VDC. Minimum

ON voltage 19.2 VAC/DC; maximum OFF voltage 5 VAC/DC. Value of

1=True/ON, Value of 0=False/OFF. Close inhibit input. Close inhibit must

be configured for OFF to use as a basic user input.

Bit 11 3/Remote Stop Input – User Input 3. Referenced as Terminal 26.

Connect with 120 VAC or 24 VDC. Minimum ON voltage 19.2 VAC/DC;

maximum OFF voltage 5 VAC/DC. Value of 1=True/ON, Value of 0=False/

OFF. Remote stop input. Remote Control must be configured for OFF to

use as a basic user input.

Bit 12 4/Remote Open Input – User Input 4. Referenced as Terminal

25. Connect with 120 VAC or 24 VDC. Minimum ON voltage 19.2 VAC/

DC; maximum OFF voltage 5 V AC/DC. Value of 1=True/ON, Value of

0=False/OFF. Remote open input. Remote Control must be configured

for OFF to use as a basic user input.

Bit 13 User Input 5/Remote Close Input – User Input 5. Referenced as

Terminal 27. Connect with 120 VAC or 24 VDC. Minimum ON voltage

19.2 VAC/DC; maximum OFF voltage 5 VAC/DC. Value of 1=True/ON,

Value of 0=False/OFF. Remote close input. Remote Control must be

configured for OFF to use as a basic user input.

Subparameter 5 uint16_var

DigitalInput_2. read only 16-bit unsigned value. Contains field unit

status and digital input status.

Bit 00 Analog Board 1 Present

Bit 01 Analog Board 2 Present

Bit 02 Analog Input 1 Lost – Indicates analog Input 1 is not receiving a

4-20 mA signal. Referenced as terminals 39 and 28 (common). Value of

1=True, Value of 0=False.

Bit 03 Analog Input 2 Lost – Indicates analog Input 2 is not receiving a

4-20 mA signal. Referenced as terminals 40 and 28 (common). Value of

1=True, Value of 0=False.

Bit 04 Undefined

Bit 05 Not Used

Bit 06 DDC Board Present – Indicates presence of optional MX/QX DDC

board. This board allows the actuator to be configured for use on the

Fieldbus network. Value of 1=True, Value of 0=False.

Bit 07 I/O Optional Board Present – Indicates presence of optional

I/O board. This board provides AR-1 to AR-3 Relays and User Inputs

6-8. This board also contains the 4-20 mA outputs for analog position

transmitter (APT) and analog torque transmitter (ATT). Value of 1=True,

Value of 0=False.

Bit 08 FF Board Present