Appendix – feature definitions, Transducer block i/o channels, Channel 1 – set actuator position – Flowserve MX FOUNDATION Fieldbus Field Unit User Manual

Page 45

Advertising
background image

45

MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11

flowserve.com

B

Appendix – Feature

Definitions

Transducer Block I/O Channels

The following section defines the Transducer Block I/O channels available for use by the function
blocks.

Channel

Channel Name

Description

0

NOT_INITIALIZED_CHAN

1

AO_CTRL_VALVE_FLOW_CHAN

Desired valve position %

2

DI_POSITION_AND_BUS_MODE_CHAN

Valve status and control mode

3

DI_POSITION_CHAN

Valve status, moving/stopped

4

DI_ACTUATOR_FAULTS_1_CHAN

Mechanical and electrical faults 1

5

DI_ACTUATOR_FAULTS_2_CHAN

Mechanical and electrical faults 2

6

DI_ACTUATOR_ALARMS_CHAN

Emergency shutdown and inhibits

7

DI_DISC_USER_INPUT_CHAN

Discrete input from user

8

DI_READ_DISC_OUTPUT_CHAN

Read discrete output

9

DO_POSITION_CHAN

Command Stop/Open/Close

10

DO_ESD_CHAN

Command Emergency Shutdown

11

DO_RELAY_CHAN

Command energize relays

12

AI_POSITION_CHAN

Current valve position (0-100%)

13

AI_ANALOG_INPUT_1_CHAN

Value of analog input 1 (0-100%)

14

AI_ANALOG_INPUT_2_CHAN

Value of analog input 2 (0-100%)

The actuator fieldbus control contains four discrete input (DI) bocks. However, as described below,
there are seven DI channels to choose from, so three channels are inactive.

Details of the channels are shown in the following tables.

Channel 1 – Set Actuator Position

The Channel 1 name is AO_CTRL_VALVE_FLOW_CHAN. Data on this channel is used to set the
position of the actuator when it is locally configured to run in the Position mode.

Control valve is in units of 0-100%.

AO_CTRL_VALVE_FLOW_CHAN will only function when the actuator is in Position mode. Position
mode is selected using the setup menus, refer to Installation and Operation Manuals LMENIM2306
for the MX and LMENIM3306 for the QX.