Appendix – feature definitions, Transducer block i/o channels, Channel 1 – set actuator position – Flowserve MX FOUNDATION Fieldbus Field Unit User Manual
Page 45
45
MX/QX FOUNdaTION Fieldbus Field Unit FCd LMENIM2330-01 – 08/11
flowserve.com
B
Appendix – Feature
Definitions
Transducer Block I/O Channels
The following section defines the Transducer Block I/O channels available for use by the function
blocks.
Channel
Channel Name
Description
0
NOT_INITIALIZED_CHAN
1
AO_CTRL_VALVE_FLOW_CHAN
Desired valve position %
2
DI_POSITION_AND_BUS_MODE_CHAN
Valve status and control mode
3
DI_POSITION_CHAN
Valve status, moving/stopped
4
DI_ACTUATOR_FAULTS_1_CHAN
Mechanical and electrical faults 1
5
DI_ACTUATOR_FAULTS_2_CHAN
Mechanical and electrical faults 2
6
DI_ACTUATOR_ALARMS_CHAN
Emergency shutdown and inhibits
7
DI_DISC_USER_INPUT_CHAN
Discrete input from user
8
DI_READ_DISC_OUTPUT_CHAN
Read discrete output
9
DO_POSITION_CHAN
Command Stop/Open/Close
10
DO_ESD_CHAN
Command Emergency Shutdown
11
DO_RELAY_CHAN
Command energize relays
12
AI_POSITION_CHAN
Current valve position (0-100%)
13
AI_ANALOG_INPUT_1_CHAN
Value of analog input 1 (0-100%)
14
AI_ANALOG_INPUT_2_CHAN
Value of analog input 2 (0-100%)
The actuator fieldbus control contains four discrete input (DI) bocks. However, as described below,
there are seven DI channels to choose from, so three channels are inactive.
Details of the channels are shown in the following tables.
Channel 1 – Set Actuator Position
The Channel 1 name is AO_CTRL_VALVE_FLOW_CHAN. Data on this channel is used to set the
position of the actuator when it is locally configured to run in the Position mode.
Control valve is in units of 0-100%.
AO_CTRL_VALVE_FLOW_CHAN will only function when the actuator is in Position mode. Position
mode is selected using the setup menus, refer to Installation and Operation Manuals LMENIM2306
for the MX and LMENIM3306 for the QX.