Names of components, 5 gfci – MMD Equipment 25S-3A3 User Manual

Page 24

Advertising
background image

2. Names of Components

2-6

2.5 GFCI

(GROUND-FAULT CIRCUIT INTERRUPTER) RECEPTACLES


Using the generator in rain, snow or near water can lead to death from electric shock. Keep the
generator dry.

All of the 20 ampere 120 volt receptacles on the generator are protected by a GFCI
(Ground-fault circuit interrupter) for protection against the hazards of ground fault
currents. An example of ground-fault current is the current which would flow through
a person who is using an appliance with faulty insulation and, at the same time, is in
contact with an electrical ground such as a plumbing fixture, wet floor, or earth.

The ground-fault circuit interrupter will not protect against short circuits or overloads.
The circuit breaker in the control panel which supplies power to the circuit provides
that protection.

The ground-fault circuit interrupter can be identified by the TEST and RESET buttons.
The receptacles on the GFCI can be tested with the TEST and RESET buttons.

TEST BUTTON: To test, depress the “TEST” button. (power is turned off)

RESET BUTTON: To restore power, depress the “RESET” button.


Perform this test monthly or every 250 hours operation whichever comes first, in order
to ensure proper operation of the GFCI receptacle. If the generator is stored outdoors,
unprotected from the weather, test the GFCI receptacle before each use. Record your
test on the GFCI test card provided on the control panel.

Advertising
This manual is related to the following products: