6. Periodic Inspection/Maintenance

6-8

6.5.3 Check GFCI Receptacles

Check GFCI receptacles monthly or 250 hours operation, whichever comes first.

If the generator is stored outdoors, unprotected from the weather, test the GFCI receptacle

before each use.

In case the GFCI has tripped due to the hazard of ground fault currents, investigate the

cause and correct it.

Regularly check the GFCI operation for safety.

(Procedure)

Unplug all appliances from the generator.

Start the engine.

Turn each single-phase and three-phase breaker
ON.

Press the TEST BUTTON

The RESET BUTTON should extend with a

click.

If the RESET BUTTON does not extend, contact

your nearest dealer.

Press the RESET BUTTON

When the RESET BUTTON extends during
operation:

Unplug all appliances from the GFCI protected

receptacle.

Press the RESET BUTTON:

IF THE GFCI CANNOT BE RESET: The GFCI is faulty. Contact your nearest dealer.
IF THE GFCI RESETS PROPERLY: Check the appliance or the power cord.