Installation, 2 auxiliary ac power – MMD Equipment 25S-3A3 User Manual

Page 28

Advertising
background image

4. Installation

4-3

Never use voltage selector switch during operation.

4.3.1 Proper Connection of Three-phase Four-wire Type Terminal



During operation, do not operate voltage selector switch. Voltage

selection during operation may cause abnormal voltage on the load

side to damage the load and may cause a fire.

In addition it could cause damage to generator and automatic

voltage regulator (AVR).

Be sure to shut off generator before using voltage selector switch.

When voltage selection is completed, lock the voltage selector

switch in position to prevent anyone from operating it.






















NOTE;
When the voltage selector switch is in the single-phase 240/120V position, place the
ammeter change-over switch to the L1 or L3 position to read the output.

4.3.2 Auxiliary AC Power

In addition to the AC single-phase power from the output
terminals, an auxiliary AC power receptacle panel is provided.
To use these receptacles, place the voltage selector switch to the
single-phase 240/120V position and adjust the output voltage to
240V with the voltage regulator at the generator control panel.

H990177

Single-phase breaker

H990305

H990188

A040153

A040154

A040155

A040156

A040157

A040158

A040161

A040159

A040160

H990181

H990177

Advertising