7. Maintenance/Adjustment

7-4

Symptom Cause Countermeasures

Even when operated
at rated speed, no
voltage or low
voltage generated.

Faulty voltmeter

Poor tightening of terminals

Broken or short-circuited winding of
generator main unit

Faulty AVR (Automatic Voltage
Regulator)

Faulty silicon rectifier (mounted on
generator rotor)

Faulty exciter

Broken or short-circuited winding of
exciter field

Check/change

Check/tighten

Check/repair

Check/change

Check/change

Check/repair

Check/repair

High voltage
generation when
generator rotates at
a rated speed.
Voltage does not
decrease even when
the automatic
voltage regulator
knob is turned.

Loosened or disconnected wiring, or
connector to AVR

Faulty AVR

Broken wire or poor contact of AVR
variable resistor

Check/connect

Check/change

Repair or change

Unstable voltage
generation.

Poor tightening of each terminal

Faulty AVR

Check/tighten

Check/change

Over speed warning
lamp goes on.

Engine speed too high

Maladjustment or failure of controller

Check/adjust

Replace or adjust

The items in time
chart (5.2.1) do not
function.

Maladjustment or failure of controller

Faulty pickup sensor

Disconnection, loosening of connectors
and cable removal

Replace or adjust
(Contact our distributor
or us)

Check/replace

Check/retighten

Three-phase breaker
will not be switched
“ON”

Output terminal cover is open

Faulty door switch

Check/

Replace

Contact your nearest dealer if you find the repair to be difficult.