H36PVN Power Vent Indoor Gas Fireplace

Page 24

XG0649 - 031511

Installation

Section 6: Installing the Gas Line

Figure 14. Gas line access. (See Figure 1,

L-H Side View)

Note: After gas line is connected, each appliance connection,

valve and valve train must be checked while under

normal operating pressure with either a liquid solution, or

leak detection device, to locate any source of leak. Tighten

any areas where bubbling appears or leak is detected until

bubbling stops completely or leak is no longer detected.

Gas line & valve: Exterior Access

The

H36PVN is supplied one (1) one exterior access Panel (LH-side

firebox) . This panel is fastened directly to the exterior of the firebox

with sheet metal screws . To remove the panel follow the steps below:

Figure 15. (Removing the Gas valve

panel hardware).

Figure 15a. (Inset)

Figure 15b. (Incoming gas supply line (supplied by Montigo)

and top of Gas valve).

Important Note: The flexible gas line supplied with the H36PV*

may not be acceptable in the jurisdiction

which this fireplace is being installed. Please

check the Local Gas codes or bylaws for the

State or Province prior to installation.

Gas Valve

Gas In, Figure 14

Exterior gas

access panel

hardware, 10-pcs.

10”

4”

3”

Flexible Input

Gasline,

(Supplied)

Back of

Fireplace

F

UEL CONVERSION

„

Verify that your fireplace is compatible with your available

gas type . (Natural Gas or Propane shown by "N" or "L" in

your model number

„

If gas type is not compatible, contact your local Montigo

representative to purchase a conversion kit .

„

Conversion kits must be installed by a qualified service

technician .

GAS PRESSURE

„

Optimum appliance performance requires proper input

pressures .

„

Gas line sizing requirements will be determined in ANSI

Z221 .3 National Fuel Gas Code in the USA and CAN/CGA

B149 in Canada .

Pressure requirements are:

„

The manifold outlet pressure is set from the factory to the

appropriate pressure but should be verified .

„

To check pressures, control valves have a provision to remove

a 1/8” N .PT . plug to be fitted with a hose barb .

„

Montigo requires a service shut off valve be located in an

accessible location to isolate the gas supply .

„

Only install gas shut-off valves approved for use by the state,

province, or other governing body in which the fireplace is

being installed .

GAS CONNECTION

„

See Figure 22 below for location of gas line access .

„

Flexible gas connectors must not exceed 3 feet in length,

unless allowable within local regulations .

„

Connect incoming gas line to the 1/2"or 3/8" gas inlet port .

„

Purge all air out of gas line .

„

Check appliance connection, valve and valve train under

normal operating pressure with a commercially available

leak check solution .

„

DO NOT USE A FLAME OF ANY KIND TO TEST FOR

LEAKS.

Pressure Requirements

Gas Pressure

Natural Gas Propane

Minimum Inlet Pressure 5 .5" W .C .

11" W .C .

Manifold Pressure

3 .5" W .C .

10" W .C .

When pressure testing the fireplace,

Gas line, and input system follow the

appropriate local codes or your area.

DO NOT connect the fireplace to

pressures in excess of 1/2lb. This will

damage the gas control valve.

NOTICE

XW2032