H36PVN Power Vent Indoor Gas Fireplace

Page 9

XG0649 - 031511

Installation

Section 4: Installing the Power Vent

Figure 4a. Multi-elbow Venting Installations.

Multi-Elbow Installations

Multi-elbow installations are possible up to a maximum of six
at 90° elbows

Figure 4b. Downward Venting Installations.

Downward Vertical Venting

Note: The downward vent run must not exceed 6' of vent run

Figure 4 Typical straight Venting Installations.

Montigo supplies a variety of power venting options The location of
the power vent should be selected and laid out to provide the shortest
possible run to an external wall or through the roof In the event that
the external power vent is not aesthetically acceptable or otherwise
infeasible, an in-line power vent can be used with this and is included
on page 17 of this instruction manual (contact Montigo for Details)

Installing a Roof Mounted Vertical Exterior Power Vent
(EDVRSPV58)

This section applies to installations where the shortest possible vent
run is through the roof Refer to Appendix A - Power Vent locations,
to ensure the planned Power vent location is acceptable Once the
vent location has been established, please refer to the appropriate
section below for installation details

Venting Layout

Selection of components and details of venting lay out should adhere
to the following guidelines:

■ Ensure there is a minimum run of 2’ of straight pipe before

the power vent

■ Ensure the maximum vent run does not exceed 80’

■ Ensure the number of 90° elbows does not exceed 6

■ Ensure the number of 45° elbows does not exceed 12

Straight Venting Layout

Venting Installation

V (Maximum Length) Max. # Elbows

100 Feet

0

Multi Elbow - Venting Installation

V1 + H1 + V2 + H2 + V3

(Maximum Length)

Max. #

Elbows

40 Feet

6

V

Elbow 1

Elbow 2

Elbow 3

Elbow 5

Elbow 4

H2

H1

V1

V2

V3

Elbow 1

Elbow 2

Elbow 3

Elbow

H1

V1

D = 6’ foot

MAX

V3

H2

Elbow 4

Multi Elbow - Venting Installation

V1 + H1 + V2 + H2 + V3

(Maximum Length)

Max. #

Elbows

80 Feet

6

WARNING:

MUST

on the door gasket and/or explosion ports will result in

products of combustion leaking into the living space and

may result in carbon monoxide poisoning.