Installation & Wiring

SA E-BUS Controller Technical Guide

12

Digital Room Sensor Wiring

Digital Room Sensor

The OE217-00 Digital Room Sensor is used to sense Space Temperature
and the OE217-01 Digital Room Sensor is used to sense Space Tem-
perature and Space Humidity. The Sensor connects to the SA E-BUS
Controller with the TSDRSC modular cable. It should be mounted at ap-
proximately 5 ft. above the fl oor on the wall in an area that does not have
drafts or is exposed to direct sunlight. See Figure 6 for wiring details.

I2C DIGITAL

SENSOR

I2C

EXPANSION

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

WattMaster Label

#LB102033-01

AI1

I1

SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

SA E-BUS Controller

Digital Room Sensor

Display

Override

OVERRIDE

ALARM

TSDRSC Cable

Note: The

Connects

Directly To The

Controller Using

A

Of The Appropriate

Length.

Digital Room Sensor

SA E-BUS

TSDRSC Cable

The Maximum Length Allowed Is

160 Feet.

EMERGENCY SHUTDOWN

Note: No Additional Wiring is Required For
Dual Cabinet Units.

Figure 6: OE217-00 & OE217-01 – Digital Room Sensor Wiring