SA E-BUS Controller Technical Guide

Additional Applications

35

Water Source Heat Pump Protection Module Overview and Wiring

Figure 28: Water Source Heat Pump Protection Module to E-BUS Distribution Module Wiring Diagram

Water Source Heat Pump Protection

Module

The Water Source Heat Pump Protection Module (OE-334-23-WPM-
A)protects the compressors on an AAON Water Source Heat Pump
unit from damage by monitoring Suction Pressure, Leaving Water
Temperature, and Water Proof of Flow. It also utilizes a Delay Timer
to prevent the compressors from turning on at the same time.

There is one water-only version of the Water Source Heat Pump
Protection Module—the OE-334-23-WPM-A which uses R-410A
refrigerant. There are also two 410-A glycol versions—the OE-334-
23-WPM-A20 which uses 20% glycol and the OE334-23-WPM-A40
which uses 40% glycol.

NOTE:

When using the WSHP Protection Module, the

compressors are wired to this module instead of the SA E-BUS
Controller and SA Expansion Module.

The Water Source Heat Pump Protection Module connects to the SA
E-BUS Controller, allowing the Water Source Heat Pump Protection
Module to receive control data and alarms from the SA E-BUS Control-
ler. See Figure 28 below for wiring diagram.

The Water Source Heat Pump Protection Module requires a 24 VAC
power connection with an appropriate VA rating.

NOTE: For complete information, including the sequence
of operation, refer to AAON Tulsa’s Water Source Heat Pump
Protection Module Technical Guide
.

NOTE:

NORMALLY

OPEN AND RATED FOR 24 VAC POWER ONLY

ALL RELAY OUTPUTS ARE

COMPRESSOR A2 ENABLE

COMPRESSOR A1 ENABLE

GND

T2

T1

R

R1

R4
R5

R3

R2

COMM

COMPRESSOR A1 SUCTION

PRESSURE TRANSDUCER

BK

RD

WH

WATER POF SYSTEM A CONTACT

BK

RD

WH

BK

RD

WH

BK

RD

WH

WATTMASTER CONTROLS

COMPRESSOR B1 ENABLE

COMPRESSOR B2 ENABLE

ALARM OUTPUT

WATER POF SYSTEM B CONTACT

BIN6
BIN7
COM

LEAVING WATER TEMPERATURE
FOR SYSTEM B

LEAVING WATER TEMPERATURE
FOR SYSTEM A

HVAC UNIT CONNECTIONS

COMPRESSOR A2 SUCTION

PRESSURE TRANSDUCER

COMPRESSOR B1 SUCTION

PRESSURE TRANSDUCER

COMPRESSOR B2 SUCTION

PRESSURE TRANSDUCER

- 1 AMP MAXIMUM LOAD

OE334-23-WPM

Water Source Heat Pump

Protection Module

Set Address to 1 When Using

One WSHP Protection

Module And Set Addresses

Consecutively if Using More

Than One. Note: Address

Zero Defaults to Address 1.

HSSC Cable

24 VAC

Transformer

3 VA Minimum

24 V

A

C

GND

Connect To Other WattMaster-

Approved E-BUS Expansion

Module(s)

HSSC Cable

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and
24 VAC-to-24 VAC.

Connect To

SA E-BUS

Controller

Line Voltage

DIGITAL STAGE 1 (1.5-5V)

AO1
AO2

DIGITAL STAGE 2 (1.5-5V)