Installation & wiring, Entering water temperature sensor wiring, Sa e-bus controller technical guide – Orion System SA E-BUS Controller User Manual

Page 15: Entering water temperature sensor

Advertising
background image

SA E-BUS Controller Technical Guide

Installation & Wiring

15

Entering Water Temperature Sensor Wiring

Figure 10: OE233 – Entering Water Temperature Sensor Installation & Wiring

Entering Water Temperature Sensor

The OE233 Entering Water Temperature Sensor must be wired as shown
in Figure 10 below for proper operation. The Entering Water Tempera-
ture Sensor is a 10K Type III thermistor sensor. The Entering Water
Temperature Sensor should be mounted in the entering water piping.

Place

Between Pipe

And Sensing Element. Pipe Should
Be Clean And Smooth To Provide
Proper Thermal Contact With
Sensing Element.

Thermal Mastic

Secure Sensor Element And Thermal
Mastic Strip To Pipe With Supplied
Wire Tie. Be Sure To Tighten Wire Tie
Snugly To Ensure Good Thermal
Contact.

Butt Splice Or Wire Nut Wire Leads And
Extend Wire To Controller Terminals. Connect
One Wire Lead To Entering Water
Temperature Terminal (AI3) At The Controller.
Secure Other Wire Lead To Ground Terminal
At The Controller. See Note 3.

Notes:

1.)Sensor Should Be Mounted At

Location Along Pipe Length
That Best Represents Desired
Temperature Reading.

3.)All Wiring To Be In Accordance

With Local And National Electrical
Codes And Specifications.

2.)Sensing Element Shown

Mounted To Top Of Pipe. The
Sensor Element May Be Located
At Any Location Around Pipe.

Wire Tire
(Supplied)

Sensing Element
(Supplied)

Thermal Mastic Strip
(Supplied)

Entering Water Pipe
See Note 1 & 2.

Caution:
For Accurate Temperature
Readings It Is Necessary To
Place Insulation Over The
Sensor After Installation.
This Prevents The Ambient
Temperature From Affecting
The Sensor. Insulation
Should Cover The Sensor
And Extend 6“ to 12”
Beyond Each End Of The
Sensor.

Entering Water

Temperature Sensor

(Strap On)

AI3

GND

Be Sure Jumper Is Set

For THERM

On AI3 For Entering

Water Temperature Sensor

AI1

AI1 SET

A

I2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

SA E-BUS Controller

Entering Water Temperature Sensor

Note: No Additional Wiring
is Required For Dual Cabinet
Units.

NOTE: For Dual Cabinet Units, mount the Entering Water
Temperature Sensor in an Entering Water Piping area that is
common to both SA Units.